Mode map home screen – Detroit Radiant Products Company MP Series User Manual

Page 9

background image

9

TH-PUI

Series

Mode Map

Home Screen

MAIN MENU

(Auto exit after 20 sec.)

SET TEMPERATURE

70°F

SElECT MOdE

ECONOMY
STANDARD
COMFORT

RUN PROGRAM

ON
OFF
ADJUST SCHEDULE
EXIT

SET dATE

DD-MMM-YY

SET TIME

12:00A

SERVICE MOdE

ENTER SERVICE
EXIT

EXIT

PROGRAM MENU

(Auto exit after 5 min.)

MONdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

TUESdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

WEdNESdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

THURSdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

FRIdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

SATURdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

SUNdAY

OCCUPIED 70°F
UNOCCUPIED 62°F

TIMING AdJUST
EXIT

SERVICE MOdE

(Auto exit after 5 min.)

SET TEMP SENSOR

LOCAL
REMOTE
HEATER

OUTdOOR SENSOR

NOT INSTALLED
INSTALLED

HIGH TEMP lOCK

ON
OFF

SET TEMP lOCKOUT

100°F

SET °F/°C dISPlAY

°F
°C

FORMAT TIME

12 Hr
24 Hr

dAYlIGHT SAVINGS

AUTO ADJUST
OFF

BACKlIGHT FORMAT

ON WITH TOUCH
ALWAYS ON

SOFTWARE VERSION

VERSION X.X

lIFETIME STATS

CYCLES: XXXXXX
HOURS: XXXXXX
FAULTS: XXXXXX
RESET STATISTICS

STATE OF CONTROl

(STATES OR ERRORS)

BldG MGMT SYSTEM

4-20mA
0-10VDC
OFF

COMMISSIONING

CODE ACCESS ONLY

RESET CONTROl

RESET TO DEFAULT
EXIT

EXIT

TIMING AdJUST

(Auto exit after 20 sec.)

WEEKdAYS

OCCUPIED 06:00A
UNOCCUPIED 05:00P

SATURdAY

OCCUPIED 08:00A
UNOCCUPIED 05:00P

SUNdAY

OCCUPIED 08:00A

UNOCCUPIED 05:00P

EXIT

COMMISSIONING

(Auto exit after 30 min.)

MOdEl OF HEATER

MP-115N V 8.0

TEST FIRING RATE

OFF
100% (BLAST)
1% (MINIMUM)

PRESSURE dIFF

0.200
% Open Gas Valve
35

EXIT