Commissioning menu – Detroit Radiant Products Company MP Series User Manual

Page 8

background image

8

TH-PUI

Series

6

Format Time: Select the desired time format from 12hr to 24hr. Factory default is 12hr.

7

daylight Savings: Select if the unit is to automatically correct for daylight savings. Factory default is off.

8

Backlight Format: This feature allows user to have the backlight on continuously or just on with the touch of
a key. In low light conditions, the continuous backlight improves contrast.

9

Software Version: This will display the software version of the Premium User Interface.

lifetime Statistics: This will allow the user to view some key statistics of the heater, such as the number of
cycles, total runtime hours, total heating hours, and number of faults. For troubleshooting purposes, user can
reset the statistics if needed.

Building Management System (BMS): The Premium User Interface can be connected to most building
management systems. This menu item allows the installer to select the type of BMS employed. In addition,
the jumper on the base must also be set to the proper type (4-20mA or 0-10VDC). For more information, see
Building Management Systems on page 13 of this manual.

Commissioning: This feature allows the installer to enter another sub-menu where they can select certain
tools for troubleshooting or commissioning. The code to enter this menu is a three (3) character code:

A. Press in sequence: Mode/Set, up arrow, down arrow.

Reset Control: This feature allows the controller to be reset to the factory default settings.

Exit Service: This will allow user to exit back to the main menu.

Commissioning Menu

1

Model of Heater: This will display the model of the Master heater as well as the heater’s software version.

2

Test Firing Rate: To assist in measuring a stable manifold pressure this feature allows the unit to be
temporarily locked into a test firing rate of 100% or 1%. Please reference the MP Series Insert Manual
(LIOMP) for proper manifold pressures.

3

Pressure differential: This feature allows the technician or installer to read the pressure differential of the
master heater as it is running. This is measured by the pressure transducer of the modulating controller.

4

% Open Gas Valve: This feature allows the technician or installer to read the heaters % open of the gas
valve as determined by the modulating controller. This is for reference only, and does not necessarily indicate
proper operation of the heater.

5

Exit: This feature will return user to the previous menu, the Service Mode Menu.