2050F Conversion Instructions

Limitations:
Float and lock commands, deviation monitor (±10 Vdc) and external feedback (±10 Vdc) are not
supported by this kit and/or MODCELL 2050. The alarm lights are not supported by this kit. MODCELL
2050 offers integral alarming capabilities with local indication.

Notes:
1. The Ramped Set-point Monitor signal from MODCELL 2050 will be 4-20 milliamps. A 62.5 ohm

precision resistor across the Quick-Scan terminal block, positions 12 to 13 is required for .25 - 1.25
Vdc.


2. This input configuration is for .25 - 1.25 Vdc where the controller supplies 24Vdc to the transmitter (2-

wire transmitter). If the controller does not supply power to the transmitter, the blue wire is not
required to be connected.


3. The controller must be equipped with a 2nd analog I/O option card.

Configuration Specifics:
The input types must be configured for volts in the "BASE CFG **MENU**". The analog input for both
process and remote set-point must be configured for .25 to 1.25 Vdc in the "INPUTS **MENU**". Both
the control and retransmission outputs must be configured for 4 - 20 mA in the "MA. OUTPT **MENU**".