2050F Conversion Instructions

WARNING

Avoid electrical shock. AC power wiring must not be
connected at the distribution panel (ac source) until all
wiring procedures are complete.

Table 1. Common I/O Configurations

QS-1300 TB
Number

Wire Color

Signal Type

MODCELL 2050
Terminal Number

Notes

4

Note 1

Blue of Blu/Blk

Transmitter Power
Supply - Positive

15

5

Note 1

Black of Blu/Blk

Transmitter Power
Supply - Negative

Not Used

6

Note 2

Black of Blk/Red

Process Input -
Negative

11 Configure

2050

process analog input

7

Note 2

Red of Blk/Red

Process Input -
Positive

14

for .25 to 1.25 Vdc

8

Note 3

White of Wht/Blk

Controller Output -
Positive

10

9

Note 3

Black of Wht/Blk

Controller Output -
Negative

9

16

Note 4

Green of Grn/Blk

Remote Set-Point -
Positive

7 Configure

2050

second analog input

17

Note 4

Black of Grn/Blk

Remote Set-Point -
Negative

4

for .25 to 1.25 Vdc

19

Note 5

Yellow of Yel/Red

Alarm Out #2 -
Common (C)

45

20

Note 5

Red of Yel/Red

Alarm Out #2 -
Normally Closed
(NC)

46

21

Note 5

Orange of Org/Red

Alarm Out #2 -
Normally Open (NO)

44

24

Note 5

Red of Brn/Red

Alarm Out #1 -
Common (C)

48

25

Note 5

Blue of Blu/Red

Alarm Out #1 -
Normally Closed
(NC)

49

26

Note 5

Red of Blu/Red

Alarm Out #1 -
Normally Open (NO)

47


Notes:
1. Used as a transmitter power supply on 1300R through 1380R, 1310C through 1330C, 1301K-1302K,

1340N-1341N instruments only.

2. Used as a process input on 1300R through 1380R, 1310 through 1330C, 1301K instruments only.
3. Used as controller output on 1300R through 1380R, 1310C through 1330C instruments only.
4. Used as remote set-point on 1300R,1310R,1340R,1350R,1320C,1330C series instruments only.
5. Used as alarm relays on 1300R, 1310R series instruments only.

2