2050F Conversion Instructions
MODCELL 2050 to Quick-Scan 1300R &1310R Series
Direct Connect Cable Option
Termination Connections to MODCELL 2050
This instruction sheet provides termination identification and locations for wiring the Quick-Scan Direct
Connect Cable to a MODCELL 2050 when replacing a 1300R/1310R Series instrument. Little or no
wiring changes need to be made on the Quick-Scan 1300 terminal block. Please read the application
notes, limitations and configuration specific instructions located at the bottom and back of this page
before proceeding. Other signals from or to MODCELL 2050 may be used via spare wires in the quick
connect cable.
WARNING
Avoid electrical shock. AC power wiring must not be
connected at the distribution panel (ac source) until all
wiring procedures are completed.
MODCELL 2050 Termination Block
Not Used
Org/Blk
Black/wht/Red
Blk
Blu
Blk/Red
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
L2
L1
29
30
31
32
33
34
35
36
37
38
39
40
16
17
25
41
42
43
44
45
46
47
48
49
Grn
Wht
Blk/Wht
Red
Wht
Blk
Grn
Power Cord
Red/Blk/Wht
Blu/Wht
Wht/Blk
Org/Red
Red/Wht
Org
Process Input [see note 3]
Output
(.25 - 1.25 Vdc)
(4 - 20 mA)
Remote Set-point Input
(.25 - 1.25 Vdc)
Set-point Monitor Active
(4 - 20 mA) [see note 1]
C
NO
NC
C
NO
NC
Alarm Output 1
Alarm Output 2
[see note 2]
[see note 2]
(AC or DC)
Limitations:
The following signals are not supported by this kit and/or MODCELL 2050; deviation monitor (±10 Vdc),
external feedback (±10 Vdc), alarm input (.25-1.25 Vdc or ±200 mV), upper and lower alarm light (24
Vdc).
Notes:
1. The Set-point Monitor signal from MODCELL 2050 will be 4-20 milliamps. A 62.5 ohm precision
resistor across the Quick-Scan terminal block, positions 12 to 13 is required for .25 - 1.25 Vdc.
4