Table 4-9. communication module – Micromod Micro-DCI: 53IT5100B Micro-DCI 4-Channel Indicator Totalizer User Manual
Page 44
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-9. Communication Module
Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity
selection, etc.).
Title
Symbol
Datapoint Default Attribute
Instrument
Address
IA B001 0
It identifies the address of this instrument on the
Datalink network. Each unit connected to the Datalink
network must have its own unique address. Valid
addresses are from 0 -31.
Baud Rate
BR
B002
253
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments connected to
the same Datalink network. Datapoint values and their
corresponding baud rates are as follows:
Value Baud
Rate Value Baud
Rate
255 28800 9 28800
254 14400 8 14400
N/A N/A 7
19200
253 9600 6 9600
250 4800 5 4800
244 2400 4 2400
232 1200 3 1200
208 600 2 600
160 300 1 300
N/A N/A 0 110
No Parity
CP
L256
0
This datapoint indicates if parity generation and
checking should be turned on or off. It is set to 0 for
even parity serial byte protocol. It is set to 1 for no parity
protocol.
No Byte
Stuffing
CB L258 0
When set to a 1, this datapoint disables the standard
communication protocol feature which inserts a 00
(NUL) byte after every 7EH (SOH) that is not the
beginning of a message. (This permits user written
communications software to determine the number of
bytes to expect in a response message.) It must be set
to 0 when using the Micro-DCI communications
software or equipment.
Datalink
Disable
DLD L257 0
When set to 0 , it permits full Datalink communication
capabilities. When set to 1, it disables Datalink
communication capabilities.
40