Table 4-8. totalizer module – Micromod Micro-DCI: 53IT5100B Micro-DCI 4-Channel Indicator Totalizer User Manual
Page 42
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-8. Totalizer Module
Purpose: The totalizers provide a running total of each analog input (ANI0-3). This module is
used to set input scaling factors, rollover and dropout values, and to define display tags for each
totalizer.
Title
Symbol
TM
Datapoint
Default
Attribute
Tag
Name
TMTAG0
TMTAG1
TMTAG2
TMTAG3
TM0
TM1
TM2
TM3
A092
A094
A096
A098
TOTAL-0
TOTAL-1
TOTAL-2
TOTAL-3
These are assignable 10 character names that
appear on the totalizer display.
Eng.
Units
TMEU0
TMEU1
TMEU2
TMEU3
TM0
TM1
TM2
TM3
A093
A095
A097
A099
UNITS
UNITS
UNITS
UNITS
These are assignable 10 character names that
appear on the totalizer display as the engineering
units of measure.
Scale
Factor
TMF0
TMF1
TMF2
TMF3
TM0
TM1
TM2
TM3
C318
C320
C322
C324
16666
16666
16666
16666
The value of the input is multiplied by this
parameter prior to being summed to the running
total. The parameter is used for both scaling and
time interval integration. For example, if ANI0 is in
M gallons/day, in order to totalize in K gallons the
scale factor (SF) would be:
SF = [Units Conversion] X [Time Base Conversion]
SF = [1000 K gal / M gal] X [(1 day/24 hrs) X (1
hr/60 mins) X (1 min/60 sec) X (1 sec/sample)] =
1000/86400 = 0.01157
NOTE: The time between totalizer updates is
one second.
The default value of 16666 uses the scale factor
for time interval integration. Due to the internal
timing of the instrument, a scale factor of 16666 will
cause the rollover total to occur once every minute.
Rollover
Value
TMM0
TMM1
TMM2
TMM3
TM0
TM1
TM2
TM3
H048
H049
H050
H051
1000000
1000000
1000000
1000000
Specifies the maximum value of the totalizer.
When the total reaches this value it is reset to
0.0; however totalizing continues. This value
must be a positive number.
Dropout
Value
TMD0
TMD1
TMD2
TMD3
TM0
TM1
TM2
TM3
C319
C321
C323
C325
0
0
0
0
When the input value is less than this value, no
change in the total occurs.
Reset
TMR0
TMR1
TMR2
TMR3
TM0
TM1
TM2
TM3
L232
L233
L234
L235
0
0
0
0
This parameter acts like a momentary switch.
When this parameter is set to 1 the total is forced
to 0.0 and then this parameter is reset to 0.
38