8.2 CONFIGURING THE 53MC5000 PCS GATEWAY PARAMETERS

To activate gateway operation in a 53MC5000 PCS, set the specified datapoint parameters (see IB
53MC5000, Section 3) as follows:

1. Set INSTRUMENT ADDRESS (IA) (B01) to a unique value for the combined Datalink/Mi-
crolink network.

2. Set BAUD (B02) to the appropriate data transfer rate index value of the Datalink net-
work:

B02

Baud Rate

9

28,800

8

14,400

7

19,200

6

9,600

5

4,800

4

2,400

3

1,200

2

600

1

300

0

110

3. Set MICROLINK COMM MODE (B448) to the appropriate data transfer rate index value
of the MicroLink network:

Mode

Mbit/s

0

2

1

1

2

0.5

3

0.25

4. Set NO PARITY (L256) as required for the Datalink network (default is EVEN PARITY).

0 for EVEN PARITY serial byte protocol.
1 for NO PARITY protocol.

5. Set DATALINK DISABLE (L257) to 0.

6. Set NO BYTE STUFF (L258) to 0.

7. Set GATEWAY MODE (L260) as required:

0 for Datalink responder mode operation.
1 for Datalink interrogator mode operation.

8. Set GATEWAY ON (L259) to 1.