120-200-350 © 1993 (Rev 5/97) Max Machinery, Inc.
Query Program Data / Load Program Data Commands
Query commands allow the computer to read program data from the indicator and load commands
allow the computer to write program data to the indicator. Each command consists of an L(load) or a
Q (query) and the two digit submenu number of the program mode sub menu illustrated on page 6.
All program mode sub menus are serially accessible except numbers 13, 15, 42, 43 and 44. These
commands are valid only in the program mode.
Decimal Points are not required by the command except for those program blocks which allow for a
floating decimal point. All other program blocks will insert the decimal point in the correct location.
Command
Response
Description
L11 aaaaa
A
Load K-factor
where
aaaaa = K-factor
(D.P. valid)
Q11
A11 aaaaa
Query K-factor
where
aaaaa = K-factor
L12 aaaaaa
A
Load Rate Multiplier
where aaaaaa = Multiplier
(D.P. valid)
Q12
A12 aaaaaa
Query Rate Multiplier
where aaaaaa = Multiplier
L14 aaaaaa bbbbbb
A
Load Analog Rate
where aaaaaa = 4 mA rate
bbbbbb = 20 mA Rate
Q14
A14 aaaaaa bbbbbb
Query Analog Rate
where aaaaaa = 4 mA rate
bbbbbb = 20 mA rate
L21 a b
A
Load Totalizer Control Input
where
a = Control Input (1-5)
b = 0 - No function
= 1 - Reset Totalizer
= 2 - Unlatch Output
= 3 - Reset and Unlatch
Q21
A21 a b ...
Query All Totalizer Control Inputs
where
a = Control Input (1-5)
b = 0 - No function
= 1 - Reset Totalizer
= 2 - Unlatch Output
= 3 - Reset and Unlatch
L22 a
A
Load Totalizer Pulse Output Speed
where
a = 0 - No Pulse
= 1 - Pulse Fast
= 2 - Pulse Medium
= 3 - Pulse Slow
RS-485 SERIAL COMMANDS