Scmpb03/scmpb04, One/two position analog i/o backpanels, Scm5b – Impulse SCMPB01 User Manual
Page 7: Isolated analog signal conditioning products
For information call 800-444-7644
52
Isolated Analog Signal Conditioning Products
SCM5B
SCMPB03/SCMPB04
One/Two Position Analog I/O Backpanels
Description
The SCMPB03 is a single channel mounting panel for the SCM5B modules.
The SCMPB04 is a dual channel mounting panel for the SCM5B modules.
They are both DIN rail compatible.
See Figures 9, and 10 for wiring diagrams, Figure 11 for schematics.
The following accessories are required for mounting one SCMPB03/04 panel
(Figure 8):
Qty
Model
Description
1
SCMXBEFE Base element with snap foot
2
SCMXSE
Side element
The following accessories are required for mounting two or more
SCMPB03/04 panels:
Qty
Model
Description
2
SCMXBEFE Base element with snap foot
2
SCMXSE
Side element
(# panels)-2
SCMXBE
Base element without snap foot
(4 x (# panels))-4 SCMXVS
Connection pins
The following DIN rail styles are available. Specify length in meters (-XX)
SCMXRAIL1-XX
EN 50022-35x7.5 (slotted steel)
SCMXRAIL2-XX
EN 50035-G32 (slotted steel)
SCMXRAIL3-XX
EN 50022-35x15 (slotted steel)
Ordering Information
Part Number Description
SCMPB03
Standard single channel backpanel. No mounting hardware
included.
SCMPB03-2
One SCMPB03 with DIN rail mounting hardware. Shipped fully
assembled. Accepts one SCM5Bxx-xx module.
SCMPB04
Standard dual channel backpanel. No mounting hardware
included.
SCMPB04-1
SCMPB04 without cold junction compensation circuits. Use
when cost savings is desired and thermocouple input modules
SCM5B37 and SCMPB47 will not be used.
SCMPB04-2
One SCMPB04 with DIN rail mounting hardware. Shipped fully
assembled. Accepts 2 SCM5Bxx-xx modules.
SCMPB04-3
SCMPB04-1 with DIN rail mounting option. See SCMPB04
and SCMPB04-2 for details.
Specifications
Operating Temperature
40°C to +85°C
ATEX Group II, Category 3
20°C to +40°C
Relative Humidity
95% non-condensing
Interface Connector:
Field
high density screw clamp, 14 AWG max
System
high density screw clamp, 14 AWG max
Figure 8: DIN Rail Mounting Elements
Figure 9: SCMPB03 Analog I/O Backpanel
Figure 10: SCMPB04 Analog I/O Backpanel