Page 11: Isolated analog signal conditioning products

background image

For information call 800-444-7644

56

Isolated Analog Signal Conditioning Products

SCM5B

SCMPB06

8-Position Analog I/O Backpanel, Multiplexed

Description

The SCMPB06 backpanel (Figure 14) can accept up to eight SCM5B modules

in any combination. It can be mounted on the SCMXRK-002 19-inch metal rack.

The SCMPB06 has two analog buses; one for analog input and one for analog

output. This two-bus configuration takes advantage of the switch controlled

outputs on the input modules and the track-and-hold inputs on the output

modules. A temperature sensor is mounted on each channel to provide cold

junction compensation for thermocouple input modules (See Figure 15 for

schematic). Field connections are terminated with four screw terminals at each

module site. Up to eight SCMPB06 backpanels may be daisy-chained. Use

SCMXCA004-XX cable for daisy chaining and connecting to host computer.
Jumpers on the SCMPB06 permit user selection of low (i.e. channels 0-7) or

high (i.e. channels 8-15) addresses.

Ordering Information

Part Number Description

SCMPB06

Standard 8-channel backpanel.

SCMPB06-1

SCMPB06 without cold junction compensation circuits. Use

when cost savings is desired and thermocouple input modules

SCM5B37 and SCM5B47 will not be used.

SCMPB06-2

SCMPB06 with DIN rail mounting option. The backpanel is

mounted on a piece of anodized aluminum, which is captured

by the SCMXBEFE DIN rail mounting elements. The

backpanel is shipped fully assembled.

SCMPB06-3

SCMPB06-1 with DIN rail mounting option. See SCMPB06

and SCMPB06-2 for details.

Figure 14: SCMPB06 Analog I/O Backpanel

Electrical

Address Selection

Module read and write addresses may be selected as low (channels 0-7) or

high (channels 8-15) using the four sets of 3 position jumpers labeled J5 through

J8. Place a jumper over the two pins furthest from the field I/O termination blocks

on all four sets to select a low address (factory configuration) or over the two

pins closest to the field I/O termination blocks on all four sets to select a high

address.
The SCMPB06 backpanel has address decoding circuitry to allow multiplexing

any combination of up to 8 input or output modules. Capability is also provided

in the address decode circuitry to expand the system to 64 channels (eight

SCMPB06 backpanels) of multiplexed input or output. Jumpers select which set

of 16 addresses are assigned to a particular backpanel. The Read Address

group assigns a set of 16 addresses for input modules, and the Write Address

group assigns a set of 16 addresses for output modules. The table below shows

the correlation of jumper position to address range. Refer to page 51 for

additional notes on the P1 connector, power requirements, fusing, and

grounding issues.

Specifications

Operating Temperature

–40°C to +85°C

ATEX Group II, Category 3

–20°C to +40°C

Relative Humidity

95% non-condensing

Interface Connector:

Field

high density screw clamp, 14 AWG max

System

26-pin, male header connector

Address Input Logic Levels:

Max Logic “0”

0.8V

Min Logic “1”

2.0V

I

I

Input Current, “0” or “1”

0.1µA max at 25°C

1.0µA max –25°C to +85°C

RD EN\ or WR EN\ Signal Delay

from Connector P1 to Channels 0-7

Standalone (address 0-7)

51ns at 25°C, 64ns at –25°C to +85°C

Expanded (address 8-63)

100ns at 25°C, 126ns at –25°C to +85°C