beautypg.com

Impulse SCMXIF User Manual

Scm7bxev, Scm7b

background image

SCM7B

Visit our website www.dataforth.com

87

Isolated Process Control Signal Conditioning Products

SCM7B

SCM7BXEV

Description

The SCM7BXEV (Figure 1 and 2) is a single channel backpanel that can accept

any of the SCM7B analog modules. It is meant to be used primarily for module

evaluation. Unlike multiple channel backpanels, the single high-level system

output (or input) signal is routed to all channel pins on the system interface

DB25 connector. The backpanel contains four standoffs to allow mounting, using

a #6 or smaller screw.

System Side - Power

Using the “V+” supply input, the power supply voltage can be as little as +14VDC.

If +15VDC is available, it is recommended that the supply be connected between

the “V+A” or “V+B” connections and “COM”; this will protect the module against

accidental supply reversal. Using both these connections with two power

supplies enables redundant operation. It is also recommended that a diode

transient absorber be installed to reduce power supply transient events from

degrading system performance. An “accessory” location, between the supply

and common lines, is provided for this purpose. The backpanel is fused at

1/4 Amp for module protection.

System Side - Signal

The SCM7BXEV uses either the SCM7BXCA01 (DB25 to 26-pin adapter

cable) and SCMXCA004-XX (26-pin to 26-pin interface cable), or the

SCM7BXCA02 (DB25 to DB25 interface cable), depending on system

requirements.

Figure 1: SCM7BXEV Dimensions

Specifications

Operating Temperature

–40°C to +85°C

ATEX Group II, Category 3

–20°C to +40°C

Relative Humidity

90%

Interface Connector:

Field

high density screw clamp, 10-24 AWG

System

DB25 (male) with 4-40 screwlocks and

high density screw clamp, 10-24 AWG

Field Side - Signal

On the field side, a temperature sensor is mounted underneath the field side

terminal block to provide cold junction compensation for thermocouple modules,

and a current-to-voltage conversion resistor (P/N SCM7BXR1) socketing

location is provided (supplied with SCM7B33 modules). Field connections are

terminated with three screw terminals

Accessories for SCM7B Analog Modules