Jumper options, E1 a e1 b – CTI Products CIB Comparator Interface User Manual
Page 16
![background image](/manuals/334824/16/background.png)
CIB Hardware Reference
Option Switches
CTI Products, Inc.
68-10854-135
10
4.5 Jumper
Options
Figure 4 shows the configuration of the two jumper options available on the rear
of the CIB. These jumpers should be installed at system installation time with
power removed from the CIB.
CA-80024-100
E1 A
E1 B
Figure 4 - Jumper Options
Jumper E1A is located across the top 2 terminals of the 6 pin terminal block.
Jumper E1B is located across the left side middle and bottom terminals of the 6
pin terminal block. The remaining 2 terminals of the block are unused.
Jumper
Function
Default
E1A
In to enable output MON 7.
Out to disable output MON 7. (For
Digitac only)
IN
E1B
In for inputs pulled up to +5 Vdc.
(Spectra-TAC w/ "B" SQMs)
Out for inputs pulled up to +15 Vdc.
IN
Table 6 - Jumper Options Description
The MON7 line conflicts with a Digitac signal. Always remove E1A when using
the CIB with a Digitac comparator.
Some Spectra-TAC comparators with the "B" version Signal Quality Module
(SQM) can be damaged when 15V is applied externally on the Disable input. For
this reason, for CIB modules shipped after January, 2003 are shipped with E1B In,
setting the input pull-up to +5 VDC.
Remove the E1B jumper if your comparator requires +15 V pull-ups.