Cashco 764PD Pressure Controller User Manual
Page 7

IOM-764P / PD
7
X
5/16”
 X = 1-27/32" (46.8mm) all ranges
except 50–150 psig = 1-25/32" (45.2mm)
Figure 10
Sensor Sub-Assembly
Assemble per these Dimensions
Figure 11
12. Install the nameplate (10) and nameplate
screw (9).
13. Install the PB needle valve (3) with a new
O-ring (7). Screw the needle valve (3) CW 
until seated, then back out to same position 
re cord ed in Table 3 prior to dis as sem bly.
14. Place a new sensor plate O-ring (6) down into
the housing (1) cavity next to the end of the 
sensor (2.1). Slide the sensor plate (15) into 
the housing (1); the fl at portion of the sensor 
plate (15) should seat against the O-ring (6). 
11. Slide the sensor sub-assembly (2) back into
the hous ing (1) so as not to damage the sensor 
O-rings (5). The fi nal position should have the 
sensor pin (2.4) directly above the center of the 
adjusting screw (2.3). Install the four end plate 
screws (8). See Figure 11.
The rounded end of the sensor plate (15) will touch 
the diaphragm (16) for the 764P, or the pusher post 
(24) of the 764PD.
NOTE: The previous description is for 764PD’s and
764P’s in pressure ranges 2" - 30" Hg, 1-30 psig, 
20-100 psig, 50-150 psig and 90-500 psig; it is 
also for 764PD’s for differential pressure ranges 
1-30, 20-100 and 50-150 psid. Refer to Figure 12 
“Di a phragm Sub-Assembly for 450-2500 psig”. 
Ob serve that the sensor plate (15) consists of a 
four part sub-assembly as follows:
15.1 Sensor
Plate
 15.2 Adaptor
 15.3 Retaining 
Ring
15.4 Spring
17. Re-engage the pneumatic housing (1) to the
di a phragm lower case (14) of the 764P, or 
the adapter (21) of the 764PD; rotate CW. 
Wrench tighten.
18. Calibrate per Section VI.