beautypg.com

Cashco Premier User Manual

Page 2

background image

IOM-148

2

TABLE 1

ACTUATOR MODEL NO. vs. VALVE BODY MODEL

(Model 48 included for clarity)

III. INSTALLATION

A. Orientation:

1. Recommended actuator major axis ori en ta tion

with any model of Cashco rotary control valve
is upwards with the valve in a horizontal pipe
and the valve stem also horizontal; i.e. position
“A” for ATO-FC, or position “B” for ATC-FO.

2. Both Ranger QCT and Premier EZO/Unlined

control valve products incorporate an ex tend ed

SECTION III

FIGURE 2: Mounting position of Ranger QCT to Model
148 Actuator with Model 73N-B P/P Positioner.

FIGURE 3: Mounting position of Ranger QCT to Model
148 Actuator with Models 9540R P/P or Smart Posi-
tioner’s PS2 and 991.

valve body bon net and a mounting yoke to
allow the actuator to be far enough away
from the valve body or mounting fl anges to
in cor po rate a minimum of 2" (50 mm) thick-
ness of in su la tion. It should not be necessary
to install thermal insulation to any portion of
Model 148 actuator. The maximum ambient
temperature for installation is 180°F (83°C);
the minimum ambient temperature is -20°F
(-29°C).

Position A

Position B

Position A

Position B

Full Actuator Model No.

Available

Bench Settings

Air Supply

Pressure

Unitized Products*

Basic

Actuator

Model No.

Modifi er

Number

psig

(Barg)

psig

(Barg)

48R

or

48D

-01

5-15

(.34-1.03)

20

(1.4)

1”-2” (DN25-50) Ranger QCT
3”-4” (DN80-100) Premier EZO or
Premier Unlined

148R

or

148D

-01

5-13

(.34-0.90)

20

(1.4)

3”-4” (DN80-100) Ranger QCT
6” (DN150) Premier EZO
or Premier Unlined

148R

or

148D

-02

10-26

(.69-1.79)

36

(2.5)

4”-8” (DN100-200) Ranger QCT,
10” (DN250) Premier EZO

148R

or

148D

-03

7.5-

19.5

(.52-1.34)

27

(1.9)

8” (DN200) Premier EZO,
8”-12” (DN200-300) Premier
Unlined

* Metric body size in parenthesis.

This manual is related to the following products: