beautypg.com

American Dryer Corp. MD-170 User Manual

Page 22

background image

18

IMPORTANT: For extended duct work runs, the cross section area of the duct can only be increased

to an extent. Maximum proportional duct work runs cannot exceed twenty (20) feet

more than the original limitations of twenty (20) feet with two (2) elbows. When the

duct work approaches the maximum limits as noted in this manual, a professional

heating venting air conditioning (HVAC) firm should be consulted for proper venting

information.

ALL duct work should be smooth inside with no projections from sheet metal screws or other obstructions

which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be

connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building.

Inspection doors should be installed at strategic points in the exhaust duct work for periodic inspection and

clean-out of lint from the duct work.

NOTE: Where the exhaust duct passes through a wall, ceiling, or roof made of combustible materials,

the opening must be 2-inches larger (all the way around) than the duct. The duct must be

centered within this opening.

a. Outside Duct Work Protection

1) To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the exhaust duct work travels vertically up

through the roof, it should be protected from the weather by using a 180° turn to point the opening

downward. In either case, allow at least twice the diameter of the duct between the duct opening and

nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside of opening of exhaust duct

work.

3. Multiple Dryer (common) Venting

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be

channeled into a "common main duct." The individual ducts should enter the bottom or side of the main

duct at an angle not more than 45° in the direction of airflow and should be spaced at least 55-1/2 inches

apart. The main duct should be tapered, with the diameter increasing before each individual 18-inch

duct is added.

IMPORTANT: The MD-170 is not provided with a back draft damper. When exhausted into a

multiple (common) exhaust line, a back draft damper must be installed at each dryer

duct.

IMPORTANT: No more than three (3) dryers should be connected to one (1) main common duct.