beautypg.com

Burkert Type 8070 User Manual

Page 19

background image

17

SettingandFunctions

9.4.2.

InP (Input) – setting the K factor of the fitting used

In this parameter, set the K factor of the fitting used, in pulses/liter.

using a pre-set value (this function is not available on a “Version 1” device. Refer to the nameplate)

When using a pre-set K factor, check that the factor indicated in the operating instructions of the fitting used is the
same as the one displayed by the 8022.

The K factors of the Bürkert sensors types 8020, 8030 and 8070 are pre-set within the 8022, for each form of the fitting S020,
S030 or S070.

Choose the sensor type associated to the 8022, then, depending on the type of sensor :

• Type 8020 – choose the fitting, material and DN
• Type 8030 – choose the material and DN
• Type 8070 – choose the DN
The pre-set K factor is displayed.

Directly setting the value of the k factor:
In the

FrEE parameter, directly enter the K factor of the fitting used. Observe the K factor given in the operating instructions of

the fitting (e.g. of type S020, S030 or S070).
After the set K factor has been confirmed using the ENTER key, the value in the

FrEE parameter is overwritten.

English

Type 8022

This manual is related to the following products: