Connection of the flow transmitter, Connection of the pulse divider – Burkert Type 8070 User Manual
Page 13
11
Assembly,Installation
terminal assignment
1
NPN
2
PNP
3
12 - 30 V DC
4
GND
Fig. 3: Terminal assignment of a version with cable gland
pin assignment
1
12 - 30 V DC
2
NPN
3
GND
4
PNP
Fig. 4: Pin assignment of the M12 male fixed connector
→
Wire the device following the possibilities described below.
7.2.1. connection of the flow transmitter
4 - 20 ma
When operating as a flow transmitter,
the npn and pnp outputs have no
function.
8022
12 - 30 V Dc
gnD
12 - 30 V Dc
Fig. 5: Connection of the flow transmitter
7.2.2. connection of the pulse divider
The pulse divider type 8022 has 1 NPN pulse output and 1 PNP pulse output. Connect the pulse divider with 3 wires.
English
Type 8022