Technical data, Conditions of use, Conformity to standards and directives – Burkert Type 8012 User Manual
Page 14: General technical data, Mechanical data
14
Technicaldata
Type 8012
6.
TechnicAl DATA
6.1.
conditions of use
Ambient temperature
-15 to +60 °C
Air humidity
< 80%, non condensated
Protection rating
• IP67 (version with M12 fixed
connector), female connector wired,
plugged in and tightened
• IP65 (version with cable gland)
6.2.
conformity to standards and
directives
The device conforms to the EC directives through the following
standards:
• EMC : EN 61000-6-2, EN 61000-6-3
• Safety: EN 61 010-1
• Vibration: EN 60068-2-6
• Shock: EN 60068-2-27
• Pressure (S012 fitting of DN06 to DN65 in PP, PVC, PVDF, brass
or stainless steel): the device can only be used in the following
cases (depending on the max. pressure, the DN of the pipe and
the fluid)
type of fluid
conditions
Fluid group 1, par. 1.3.a
DN ≤ 25 only
type of fluid
conditions
Fluid group 2 par. 1.3.a
DN ≤ 32
or DN > 32 and PNxDN ≤ 1000
Fluid group 1 par. 1.3.b
PNxDN ≤ 2000
Fluid group 2 par. 1.3.b
DN ≤ 200
6.3.
General technical data
6.3.1. mechanical data
component
material
SE12 electronic housing
PPS
Cable gland, M12 fixed
connector
PA
Cable, 1 m
PVC, T
max
= 80 °C
Seal exposed to the fluid
FKM (EDPM on request)
Seal exposed to the ambient air
EDPM
Paddle-wheel holder
PVDF
Paddle-wheel
PVDF
Paddle-wheel axis and
bearings
ceramic
Body of the S012 fitting
stainless steel (316L/DIN1.4404),
brass, PVC, PP, PVDF
Screws
Stainless steel A4
English