NOTE:
The K factor makes it possible to standardise the output
frequency of the floe sensor to the flow.
Q
flow
k
K factor
f
Output frequency of the flow sensor
The K factor defines the number of pulses per volume unit:
You can find the K factor in the data sheet of the flow sensor
being used.
The volume unit of the K factor determines the flow unit, e.g.,
Type 8020 with DN 25 PVC fitting (see Table 2, Page 24)
gives the flow value in litres per time unit
7.3.2 Multiplier of the K Factor
The display only displays values in the range from 0 to 199,99. With the multiplier
(upper row of bars), you can extend the display by a factor of 10.
Q
1
k
f
Multiplier = 1
Multiplier = 10
Change the multiplier
proceed to set the K factor
k
Impuls
V
Pulse
k
46,60
Impulse
Liter
Pulse
Litre
Fig. 11: Multiplier of the K Factor
- Type 1062 (112 pages)
- Type 1050 (4 pages)
- Type 8750 (64 pages)
- Type 8750 (82 pages)
- Type 8681 (90 pages)
- Type 8681 (40 pages)
- Type 8798 (2 pages)
- Type 8791 (4 pages)
- Type 8798 (106 pages)
- Type 8791 (15 pages)
- Type 8792 (136 pages)
- Type 8792 (252 pages)
- Type 8718 (34 pages)
- Type 8792 (118 pages)
- Type 8791 (106 pages)
- Type 8791 (184 pages)
- Type 8791 (28 pages)
- Type 8791 (21 pages)
- Type 8791 (154 pages)
- Type 0911 (64 pages)
- Type 0911 (84 pages)
- Type 0911 (76 pages)
- Type 0911 (46 pages)
- Type 1058 (31 pages)
- Type 1060 (4 pages)
- Type 1066 (112 pages)
- Type 1067 (158 pages)
- Type 1077-2 (33 pages)
- Type 1094 (82 pages)
- Type 1094 (126 pages)
- Type 1094 (12 pages)
- Type 1094 (41 pages)
- Type 1115 (25 pages)
- Type 1150 (99 pages)
- Type 1541 (2 pages)
- Type 5142 (6 pages)
- Type 8619 (40 pages)
- Type 8619 (134 pages)
- Type 8620 (177 pages)
- Type 8622 (4 pages)
- Type 8623 (130 pages)
- Type 8625 (118 pages)
- Type 8624 (124 pages)
- Type 8718 (4 pages)