beautypg.com

Burkert Type 1078-2 User Manual

Page 8

background image

28

For example:

The time range for t

on

is set to 5-100 seconds and the

time range for t

off

is set to 1,5-30 minutes.

If t

on

= 50 seconds = min. value of the range (5 s)

+ 45 s (45/95*100 = 47 % of the range), set the
cursor of the t

on

potentiometer as follows:

t

on

= min. value of the range + 47 % of the time range

1

3

If t

off

= 20 seconds = min. value of the range (1,5

min.) + 18,5 min. (18,5/28,5*100 = 65 % of the
range), set the cursor of the t

off

potentiometer as

follows:

1

3

t

ooff

= min. value of the range + 65 % of

the time range

Fig. 11: Setting example of potentiometers t

on

and t

off

of

the 1078-1

English

29

9.3. Adjustment of the 1078-2

To change the parameters of the 1078-2, install a configu-
ration module type 1077-2 on the timer 1078-2.

Switch off the power supply of the 1078-2 in order not
to damage the current 1078-2 settings.

Check that both red LEDs are OFF.

Loosen the screw from the 1078-2.

Remove the cover.

Install the 1077-2 with its seal onto the 1078-2, in any
position. See Fig. 6, page 21.

Insert the screw supplied with the 1077-2.

Tighten the screw at a torque rating between 0,5 and
0,8 Nm.

English

29

30

9.3.1.

Adjustment keys of the 1077-2

+

To access the Settings level.

• From the Read level to go to the next time.

• From the Settings level to go to the next

function.

• To validate the setting of each function.

• At the end of the adjustment, to transfer the

new settings to the timer.

At the Settings level:

• To change the flashing numerical value.

• To go to the next choice of a function.

Fig. 12: Adjustment of the 1077-2

English

31

9.3.2.

Display elements of the 1077-2

h m s

199:99

Time units for the displayed time:

hours, minutes and/or seconds

- At the Read level:

Shows that the output is

closed

- At the Settings level:

Shows that the ON/OFF

contact is normally open

Setting for the reset
input

Shows a time. If "--:--"
is displayed the set
cycle is completed.

Shows that the device
is beeing adjusted

Shows the operating
mode

- At the Read level:

Shows that the output

is open

- At the Settings level:

Shows that the ON/OFF

contact is normally closed

Fig. 13: Display of the 1077-2

9.3.3.

Operating levels

The configuration module has two operating levels: The
Read level and the Settings level.

English

31

This manual is related to the following products: