NOTE

* Hidden parameters
You can reach these if you hold down the buttons SET+ for 5 s
in the programming level HY. The message

Pr2 appears.

ALd

Alarm delay

0 ... 255 min; Minimum time in which the

at temperature

conditions for an alarm situation

Overshoot/Undershoot

must be present.

ALL

Low temperature alarm

-50 °C / -58 °F
Ald - Low temperature alarm after
delay time ALd

ALU

Over-temperature alarm

150 °C / 302 °F
High temperature alarm after
delay time ALd

ALc

Configuration

rE = relative to the set-value SET

Temperature alarm

Ab = Absolute

RES

Resolution

in = 1 °C; dE = 0.1 °C

CF

Temperature units

0 = degrees Celsius; 1 = degree
Fahrenheit
If the units have been changed,
you must check the set-value SET, as
well as LS, US, ALU, ALL and Ot.

CH

Effect

CL = Cooling, Ht = Heating

*COF

Switch-off period of the relay

0 ... 255 s;

with defective sensor

COF = 0: Relay always active

*COn

Switch-on period of the relay

0 ... 255 s; Default value for the relay

with defective sensor

operation period for a fixed output value
with defective room sensor
COn = 0: Relay always off

AC

Minimum switch-off period

0 + 50 min relay switch-off period

*Ods

Relaiy delay after
putting into operation

O t

Calibration of the room
sensor

-12.0 +12.0 °C / -120 °F +120 °F

*US

Highest set-value setting

Set-value limits for operator

*LS

Lowest set-value setting

Set-value limits for operator