English – Burkert Type TAT002 User Manual
Page 9
0911 - 7
english
*
*
*
NOTE
* Hidden parameters
You can reach these if you hold down the buttons SET+ for 5 s
in the programming level HY. The message
Pr2 appears.
ALd
Alarm delay
0 ... 255 min; Minimum time in which the
at temperature
conditions for an alarm situation
Overshoot/Undershoot
must be present.
ALL
Low temperature alarm
-50 °C / -58 °F
Ald - Low temperature alarm after
delay time ALd
ALU
Over-temperature alarm
150 °C / 302 °F
High temperature alarm after
delay time ALd
ALc
Configuration
rE = relative to the set-value SET
Temperature alarm
Ab = Absolute
RES
Resolution
in = 1 °C; dE = 0.1 °C
CF
Temperature units
0 = degrees Celsius; 1 = degree
Fahrenheit
If the units have been changed,
you must check the set-value SET, as
well as LS, US, ALU, ALL and Ot.
CH
Effect
CL = Cooling, Ht = Heating
*COF
Switch-off period of the relay
0 ... 255 s;
with defective sensor
COF = 0: Relay always active
*COn
Switch-on period of the relay
0 ... 255 s; Default value for the relay
with defective sensor
operation period for a fixed output value
with defective room sensor
COn = 0: Relay always off
AC
Minimum switch-off period
0 + 50 min relay switch-off period
*Ods
Relaiy delay after
putting into operation
O t
Calibration of the room
sensor
-12.0 +12.0 °C / -120 °F +120 °F
*US
Highest set-value setting
Set-value limits for operator
*LS
Lowest set-value setting
Set-value limits for operator