English, 3 electrical connections – Burkert Type TAT002 User Manual
Page 13

0911 - 11
english
Fig. 4.2: Installation sequence
Panel
Mounting frame
Front seal
4.3
Electrical connections
Use cable with a cross-section of max. 2.5 mm
2
.
Check the auxiliary power before connection the voltage supply
(see Chapter
Technical data).
Do not load the relay contacts higher than permitted. If necessary, use a
contactor.
SENSOR CONNECTIONS
Mount the tips of the sensors pointing upwards. This will prevent the
collection of liquids or condensate.
Do not mount the room sensors in an airflow. This could lead to incorrect
measurements of the average room temperature.