English, 4 controlling the loads – Burkert Type TAT002 User Manual
Page 10
8 - 0911
english
HEATING
Parameter CH = HT; The value HY has been preset to 2 K at the factory.
If the temperature falls below the value SET-HY, the controller output will be
switched on and will be switched off again when SET is exceeded.
Fig. 2.3: Heating
2.4
Controlling the loads
CONTROLLER OUTPUT
The regulation is dependent on the measured temperature (= sensor
temperature). You can program the control direction (heating or cooling) with
the parameter CH.
CH = CL
Cooling
CH = HT
Heating
COOLING
Parameter CH = CL; The value HY has been preset to 2 K at the factory.
If the temperature exceeds the value SET+HY, the compressor will be
switched on, and SET will be switched off again with temperature undershoot.
Fig. 2.2: Cooling
t
temperature
compressor
SET
SET+HY
ON
t
ON
t
t
temperature
SET
SET-HY
heat