BJM Pumps SX75CSS-575T User Manual
Page 34
START-UP REPORT FORM
Are guide rails vertical?
Yes
No
Is base elbow installed level?
Yes
No
Liquid level controls: Model
Is control installed away from turbulence?
Yes
No
Float Operation Check
Tip lowest float (stop float), all pumps should remain off.
Tip second float (and stop float), one pump comes on.
Tip third float (and stop float), both pumps on (alarm on simplex).
Tip fourth float (and stop float), high level alarm on (omit on simplex).
Check here if using manual on/off only.
Does liquid level ever drop below volute top?
Yes
No
Control Panel MFG & model no.
Number of pumps operated by control panel
NOTE: At no time should hole be made in top of control panel, unless proper sealing
devices are utilized.
Short Circuit protection:
Type:
Number and size of short circuit device(s)
Amp rating:
Overload type:
Size:
Amp rating:
Do protective devices comply with pump motor amp
rating?
Yes
No
Are all pump connections tight?
Yes
No
Is the interior of the panel dry?
Yes
No
If No, correct moisture problem.
Electrical readings
SINGLE PHASE
Voltage supply at panel line connection, pump off L1
L2
Voltage supply at panel line connection, pump on L1
L2
Amperage load connection, pump on
L1
L2
THREE PHASE
Voltage supply at panel line connection, pump off
L1-L2
L2-L3
L3-L1
Voltage supply at panel line connection, pump on
- SX75CSS-460T SX75CSS-230T SX55CSS-575T SX55CSS-460T SX55CSS-230T SX55CSS-208T SX37CSS-575T SX37CSS-460T SX37CSS-230T SX37CSS-208T SX22CSS-575T SX22CSS-460T SX22CSS-230T SX22CSS-208T SX15CSS-575T SX15CSS-460T SX15CSS-230T SX15CSS-208T SX1500CSS-230 SX750CSS-230 SX750CSS-115 SX08CSS-575T SX08CSS-460T SX08CSS-230T SX08CSS-208T S75C-575T S75C-460T S75C-230T S55C-575T S55C-460T S55C-230T S55C-208T