DE DIETRICH AWHP-2 MIT-IN-2 iSystem User Manual
Page 31
n Performances in hot mode with outside air temperature
at +2°C and outlet water temperature at +35°C (in
accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A2/W35
kW
3.76 3.87
5.93
10.19
10.19
11.38
11.38
11.62 14.70
COP hot - A2/W35
3.32 3.26
3.20
3.20
3.20
3.27
3.27
3.01
3.10
Absorbed electrical power - A2/W35 kWe 1.13 1.19
1.85
3.19
3.19
3.48
3.48
3.86
4.74
Nominal amperage - A2/W35
A
6.1
6.1
8.2
10.7
6.2
14.6
8.4
9.7
11.8
n Performances in cold mode with outside air
temperature at +35°C and outlet water temperature at
+18°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Cooling output
kW
3.84 4.69
7.90
11.16
11.16
14.46
14.46
17.65 22.2
EER
3.80 3.80
3.99
4.68
4.68
4.43
4.43
3.8
3.8
Absorbed electrical power kWe 0.72 1.15
2.0
2.35
2.35
3.65
3.65
4.65
5.84
n General values
AWHP
4 MR
6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR
27 TR
Sound pressure
(1)
dB(A) 41.7
41.7
43.2
43.4
43.4
47.4
47.4
51.8
53
Nominal water flow
(ΔT = 5K)
m
3
/h 1.04
1.04
1.47
1.88
1.88
2.67
2.67
3.8
4.6
Manometric height
available at nominal
flow rate
mbar 618
618
493
393
393
213
213
-
-
Nominal air flow rate m
3
/h 2100
2100
3000
6000
6000
6000
6000
8400
8400
Power voltage of the
outdoor unit
V
230 V~ 230 V~ 230 V~ 230 V~
400 V3~ 230 V~
400 V3~ 400 V3~
400 V3~
Sound output
(2)
dB(A) 63.7
63.7
65.2
65.4
65.4
69.4
69.4
73.8
75
R410A refrigerant
kg
2.1
2.1
3.2
4.6
4.6
4.6
4.6
7.1
7.7
refrigerant piping
connection (Liquid-
Gas)
inch
1/4-1/2 1/4-1/2 3/8-5/8 3/8-5/8
3/8-5/8
3/8-5/8
3/8-5/8
3/8-3/4 or
3/8-1
1/2-3/4 or
1/2-1
Max pre-loaded
length
m
10
10
10
10
10
10
10
30
30
Weight (empty) -
Outside unit
kg
42
42
75
118
118
130
130
135
141
(1) 5 m from the appliance, free field.
(2) Test conducted in accordance with the standard NF EN 12102
AWHP-2 MIT-IN-2 iSystem
6. Technical specifications
31/03/2014 - 7616372-001-02
30