6 Technical specifications
6.1
Technical specifications
6.1.1.
Electricity supply
230 V AC (+/- 10%) - 50 Hz
400 V AC (+ 6%, - 10%) - 50 Hz (depending on the model)
6.1.2.
Heat pump
Conditions of use:
4
Limit operating temperatures in Hot mode:
-
Water: +18 °C / +55 °C
-
Outside air:
-15 °C / +35 °C (4, 6 kW)
-20 °C / +35 °C (8, 11, 22, 27 kW)
4
Limit operating temperatures in Cooling mode:
-
Water: +7 °C / +25 °C
-
Outside air: +15 °C / +40 °C (At less than 18°C, it is necessary
to use the HK24 insulation kit option)
4
Maximum operating pressure: 3 bar
n Performances in hot mode with outside air temperature
at +7°C and outlet water temperature at +35°C (in
accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A7/W35
kW
3.72 5.87
8.26
10.56
10.56
14.19
14.19
19.4
24.4
COP hot - A7/W35
4.30 4.18
4.27
4.30
4.30
4.22
4.22
3.94
3.90
Absorbed electrical power - A7/W35 kWe 0.87 1.41
1.93
2.46
2.46
3.36
3.36
4.92
6.26
Nominal amperage - A7/W35
A
4.11 6.57
8.99
11.81
11.81
16.17
16.17
7.75
9.86