Caution: Do not charge to achieve subcooling temperature when the TXV is overfeeding. If the TXV is overfeeding,
readings may still indicate low subcooling and low superheat, but circuit may not be undercharged.
Run
Compressor
for 5 Minutes
Is Superheat
in Range?
Yes
No
Is Subcooling
in Range?
Yes
No
Is Superheat
Low or High?
High
Low
Turn TXV
Adjustment
Stem Clockwise
Is Subcooling
Low or High?
High
Low
Add Refrigerant
Is Subcooling
Low or High?
High
Low
Recheck Superheat
and Complete
Start-up and
Warranty Form
Add Refrigerant
Remove
Refrigerant
Turn TXV
Adjustment Stem
Counter Clockwise
Startup Documentation