Chilled Water Temperature

Modudes are designed for a leaving water temperature
range from 40°F to 62°F. All cataloged modules can operate
safely in this range without the need of special controls or
glycol additives. Leaving water temperatures below 40°F
can result in evaporator suction temperatures below the
freezing point of water. Therefore, a glycol solution additive
is required that will protect the evaporator from freeze ups
at lower operating suction temperatures. The full range of
leaving chiller fl uid using glycol is 20°F to 62°F.

Hydronic Refrigeration

Figure 1 - Chilled Water Circuit

Note: Figure 1 depicts hydronic piping in each ClimaCool chiller module and is shown with water isolation valves.

Service Ports (3/4”)

Isolation Ball Valves

(2 or 2-1/2”)

Pete’s Ports

Heat Exchanger

Leaving Chilled Water

Temperature Sensor

Refrigerant Circuit #1

Refrigerant Circuit #2

Water Temperature Requirement and Hydronic Refrigeration