Water piping confi gurations – ClimaCool UCA Manual User Manual
Page 13

13
www.climacoolcorp.com
Water Piping Confi gurations
Notes:
1.
Figures 1 and 2 are required piping for proper water regulation and distribution through ClimaCool modular chillers.
2.
Module order and incoming/outgoing water
fl ow, as shown in both Figure 1 and 2, can be set up as either a left-to-right or right-to-left
con
fi guration.
3.
For chilled water (evaporator) inlet/outlet location dimensions, refer to page 7 - Dimension Data and Drawings.
4.
A pressure di
ff erential
fl ow sensor or switch is a required safety device for ClimaCool modular chillers on the chilled water circuit.
5.
A strainer with a minimum of 60 mesh stainless steel screen is a required safety to protect the brazed plate heat exchanger
on the chilled water
side of the system and must be in place at all times when the chiller is operating.
6. Maximum water
fl ow rates for the evaporator water header system in one bank of modules is 1,000 GPM.
Figure 1- Field Piping Direct Return - 1 to 5 Modules
Figure 2 - Field Piping Reverse Return -(Preferred 1 to 5 modules) Required for more than 6 modules