The W&T Portable Calibrator eliminates the need for
special arrangements or external controls. The carry-
ing case has a compartment for adapters, tubing, and
other accessories; the case cover is easily removed.
Complete information on the use of the calibrator is
given in an instruction book. A schematic flow dia-
gram on the panel shows the calibrator’s connections
at a glance.

USES OF THE W&T PORTABLE
CALIBRATOR

Simplest use of the calibrator is to carry it to an on-
stream gauge, indicator, or recorder. Calibration of
such instruments can be quickly checked by making
simple connections without taking the instrument out
of service. Also, the calibrator can simulate the set
and process-variable signals to a pneumatic control
device and check its output. These three pressures
can be read out and checked in any order and in
rapid sequence. By evacuating the calibrator, abso-
lute pressure measurements can be made.

PUBLICATION

TI 650.504DE

Calibrator Uses

3

Calibration of a pressure transmitter

Using a common supply pressure for both the cali-
brator and the transmitter, transmitter input is
regulated to the desired value and held. Transmit-
ter output is accurately indicated by the calibrator.

Calibration of a gauge, indicator or recorder

Test pressure is applied to the instrument and to
the calibrator simultaneously. Instrument and cali-
brator readings are compared for an accuracy
check.

Calibration of a differential pressure transmitter

The transmitter’s supply and high-input pressures
are regulated to the desired values and held.
Transmitter output is indicated accurately by the
calibrator.

Calibration of a typical stacked diaphragm
pneumatic controller

Controller supply pressure is regulated to the de-
sired value and held. Controller set and measured
inputs and output A are regulated to the desired
value and held. The calibrator then reads out con-
troller output accurately. P

3

equals P

2

for any value

of P

2

if the controller is in calibration.

Calibration of a ratio relay

The ratio relay’s input and reference pressures are
regulated to the desired values and held. Relay
output is indicated accurately by the calibrator.

Pressure

Transmitter

3-15 psi output

Air supply P

1

P

3

Input

Regulator

Supply

Regulator

500-psi gauge

supply

(May also be connected to P

2

)

Air supply

P

1

Low pressure input (atmosphere for test)

Differential

pressure

transmitter

supply

Air supply

High pr

essur

e input

3-15 psi output

P

1

P

2

P

3

Supply

Set

Input

Output A

Output B
Measured

Input

Air supply

P

1

P

2

P

3

Output

Reference pressure if required

Air supply

P

1

P

2

P

3

Ratio replay

Supply

Input