NESLAB

NESLAB

NESLAB

NESLAB

ThermoFlex 3500

ThermoFlex 5000

ThermoFlex 7500

ThermoFlex 10000

Standard Temperature Range

+5°C to +40°C

+5°C to +40°C

+5°C to +40°C

+5°C to +40°C

(+41°F to +104°F)

(+41°F to +104°F)

(+41°F to +104°F)

(+41°F to +104°F)

Optional Temperature Range

+5°C to +90°C

+5°C to +90°C

+5°C to +90°C

+5°C to +90°C

(+41°F to +194°F)

(+41°F to +194°F)

(+41°F to +194°F)

(+41°F to +194°F)

Ambient Temperature Range

+10°C to +40°C

+10°C to +40°C

+10°C to +40°C

+10°C to +40°C

(+50°F to +104°F)

(+50°F to +104°F)

(+50°F to +104°F)

(+50°F to +104°F)

Temperature Stability

±0.1°C

±0.1°C

±0.1°C

±0.1°C

Standard Cooling Capacity
60 Hz at +20°C

3500 W / 11953 BTU

5000 W / 17076 BTU

7500 W / 25575 BTU

10000 W / 34100 BTU

50 Hz at +20°C

3050 W / 10416 BTU

4400 W / 15027 BTU

6425 W / 21910 BTU

8500 W / 28985 BTU

Reservoir Volume

1.9 gallons (7.2 liters)

1.9 gallons (7.2 liters)

4.75 gallons (17.9 liters)

4.75 gallons (17.9 liters)

Refrigerant

R407C

R407C

R407C

R407C

Physical Dimensions (H x W x D)

Air-Cooled

38.9 x 19.3 x 30.9 in

38.9 x 19.3 x 30.9 in

52.3 x 25.2 x 33.8 in

52.3 x 25.2 x 33.8 in

(98.7 x 48.8 x 78.4 cm)

(98.7 x 48.8 x 78.4 cm)

(132.7 x 63.9 x 85.6 cm)

(132.7 x 63.9 x 85.6 cm)

Water-Cooled

38.9 x 19.3 x 30.9 in

38.9 x 19.3 x 30.9 in

45.9 x 25.2 x 33.8 in

45.9 x 25.2 x 33.8 in

(98.7 x 48.8 x 78.4 cm)

(98.7 x 48.8 x 78.4 cm)

(116.6 x 63.9 x 85.6 cm)

(116.6 x 63.9 x 85.6 cm)

P1 — Positive Displacement Pump
60 Hz

2.1 gpm @ 60 psig

(7.9 lpm @ 4.1 bar)

50 Hz

1.7 gpm @ 60 psig

(6.4 lpm @ 4.1 bar)

P2 — Positive Displacement Pump
60 Hz

4.0 gpm @ 60 psig

4.0 gpm @ 60 psig

4.0 gpm @ 60 psig

4.0 gpm @ 60 psig

(15.1 lpm @ 4.1 bar)

(15.1 lpm @ 4.1 bar)

(15.1 lpm @ 4.1 bar)

(15.1 lpm @ 4.1 bar)

50 Hz

3.3 gpm @ 60 psig

3.3 gpm @ 60 psig

3.3 gpm @ 60 psig

3.3 gpm @ 60 psig

(12.5 lpm @ 4.1 bar)

(12.5 lpm @ 4.1 bar)

(12.5 lpm @ 4.1 bar)

(12.5 lpm @ 4.1 bar)

T1 — Turbine Pump**
60 Hz

3.5 gpm @ 60 psid

3.5 gpm @ 60 psid

(13.2 lpm @ 4.1 bar)

(13.2 lpm @ 4.1 bar)

50 Hz

2.5 gpm @ 60 psid

2.5 gpm @ 60 psid

(9.5 lpm @ 4.1 bar)

(9.5 lpm @ 4.1 bar)

P3 — Centrifugal Pump**
60 Hz

10 gpm @ 32 psid

10 gpm @ 32 psid

10 gpm @ 32 psid

10 gpm @ 32 psid

(37.9 lpm @ 2.2 bar)

(37.9 lpm @ 2.2 bar)

(37.9 lpm @ 2.2 bar)

(37.9 lpm @ 2.2 bar)

50 Hz

10 gpm @ 20 psid

10 gpm @ 20 psid

10 gpm @ 20 psid

10 gpm @ 20 psid

(37.9 lpm @ 1.4 bar)

(37.9 lpm @ 1.4 bar)

(37.9 lpm @ 1.4 bar)

(37.9 lpm @ 1.4 bar)

P4 — Centrifugal Pump**
60 Hz

15 gpm @ 57 psid

15 gpm @ 57 psid

(56.8 lpm @ 3.9 bar)

(56.8 lpm @ 3.9 bar)

50 Hz

15 gpm @ 34 psid

15 gpm @ 34 psid

(56.8 lpm @ 2.3 bar)

(56.8 lpm @ 2.3 bar)

P5 — Centrifugal Pump**
60 Hz

20 gpm @ 60 psid

20 gpm @ 60 psid

(75.7 lpm @ 4.1 bar)

(75.7 lpm @ 4.1 bar)

50 Hz

20 gpm @ 35 psid

20 gpm @ 35 psid

(75.7 lpm @ 2.4 bar)

(75.7 lpm @ 2.4 bar)

Unit Weight (for pump type P2 only)

264 lb (120 kg)

264 lb (120 kg)

356 lb (161.5 kg)

356 lb (161.5 kg)

Voltage Options
115 V/60 Hz & 100 V/50 Hz

1,2

100 V/60 Hz & 100 V/50 Hz

1,2

208-230 V/60 Hz & 200 V/50 Hz

1,2

Available

Available

230 V/50 Hz

1

Available

Available

200-230 V/50-60 Hz Global Voltage

1,2

Available

Available

208-230 V/60 Hz/3 phase

1,2

Available

Available

400 V/50 Hz/3 phase

1

Available

Available

400-460 V/50-60 Hz/3 phase Global Voltage

1,2

Available

Available

Standard Compliance

1

CE compliant

(for all ThermoFlex recirculating chillers)

105974_C_000

2

CSA compliant

S

p

e

c

ifi

c

a

tio

n

s

Tr

im

th

is

p

a

g

e

sh

o

rt

(7

.6

25

in

c

h

e

s)

to

a

c

c

o

m

o

d

a

te

p

o

te

n

ti

a

l

h

o

le

p

u

n

c

h

in

g

b

y

e

n

d

u

se

rs

Specifications obtained at sea level using water as the recirculating fluid, at a +20°C process setpoint, +25°C ambient condition, at nominal operating voltage.
Other fluids, process temperatures, ambient temperatures, altitude or operating voltages will affect performance. Cooling capacity based on units with
P2 pumps with no backpressure. Other pumps will affect cooling capacity performance. Specifications subject to change.
**Pressure values for centrifugal and turbine pumps are differential pressures between the inlet and the outlet of the unit.