Thermo Scientific NESLAB ThermoFlex Recirculating Chillers

NESLAB

NESLAB

NESLAB

ThermoFlex 900

ThermoFlex 1400

ThermoFlex 2500

Standard Temperature Range

+5°C to +40°C

+5°C to +40°C

+5°C to +40°C

(+41°F to +104°F)

(+41°F to +104°F)

(+41°F to +104°F)

Optional Temperature Range

+5°C to +90°C

+5°C to +90°C

(+41°F to +194°F)

(+41°F to +194°F)

Ambient Temperature Range

+10°C to +40°C

+10°C to +40°C

+10°C to +40°C

(+50°F to +104°F)

(+50°F to +104°F)

(+50°F to +104°F)

Temperature Stability

±0.1°C

±0.1°C

±0.1°C

Standard Cooling Capacity
60 Hz at +20°C

900 W / 3074 BTU

1400 W / 4781 BTU

2500 W / 8538 BTU

50 Hz at +20°C

750 W / 2561 BTU

1170 W / 3996 BTU

2200 W / 7513 BTU

Reservoir Volume

1.9 gallons (7.2 liters)

1.9 gallons (7.2 liters)

1.9 gallons (7.2 liters)

Refrigerant

R134A

R134A

R134A

Physical Dimensions (H x W x D)

Air-Cooled

27.3 x 14.2 x 24.6 in

27.3 x 14.2 x 24.6 in

29.0 x 17.2 x 26.5 in

(69.2 x 36.0 x 62.4 cm)

(69.2 x 36.0 x 62.4 cm)

(73.6 x 43.6 x 67.3 cm)

Water-Cooled

27.3 x 14.2 x 24.6 in

29.0 x 17.2 x 26.5 in

(69.2 x 36.0 x 62.4 cm)

(73.6 x 43.6 x 67.3 cm)

P1 — Positive Displacement Pump
60 Hz

2.1 gpm @ 60 psig

2.1 gpm @ 60 psig

2.1 gpm @ 60 psig

(7.9 lpm @ 4.1 bar)

(7.9 lpm @ 4.1 bar)

(7.9 lpm @ 4.1 bar)

50 Hz

1.7 gpm @ 60 psig

1.7 gpm @ 60 psig

1.7 gpm @ 60 psig

(6.4 lpm @ 4.1 bar)

(6.4 lpm @ 4.1 bar)

(6.4 lpm @ 4.1 bar)

P2 — Positive Displacement Pump
60 Hz

4.0 gpm @ 60 psig

4.0 gpm @ 60 psig

4.0 gpm @ 60 psig

(15.1 lpm @ 4.1 bar)

(15.1 lpm @ 4.1 bar)

(15.1 lpm @ 4.1 bar)

50 Hz

3.3 gpm @ 60 psig

3.3 gpm @ 60 psig

3.3 gpm @ 60 psig

(12.5 lpm @ 4.1 bar)

(12.5 lpm @ 4.1 bar)

(12.5 lpm @ 4.1 bar)

T1 — Turbine Pump**
60 Hz

3.5 gpm @ 60 psid

3.5 gpm @ 60 psid

3.5 gpm @ 60 psid

(13.2 lpm @ 4.1 bar)

(13.2 lpm @ 4.1 bar)

(13.2 lpm @ 4.1 bar)

50 Hz

2.5 gpm @ 60 psid

2.5 gpm @ 60 psid

2.5 gpm @ 60 psid

(9.5 lpm @ 4.1 bar)

(9.5 lpm @ 4.1 bar)

(9.5 lpm @ 4.1 bar)

P3 — Centrifugal Pump**
60 Hz

50 Hz

P4 — Centrifugal Pump**
60 Hz

50 Hz

P5 — Centrifugal Pump**
60 Hz

50 Hz

Unit Weight (for pump type P2 only)

130.5 lb (59.2 kg)

130.5 lb (59.2 kg)

175.5 lb (79.6 kg)

Voltage Options
115 V/60 Hz & 100 V/50 Hz

1,2

Available

Available

100 V/60 Hz & 100 V/50 Hz

1,2

Available

Available

208-230 V/60 Hz & 200 V/50 Hz

1,2

Available

Available

Available

230 V/50 Hz

1

Available

Available

Available

200-230 V/50-60 Hz Global Voltage

1,2

Available

Available

Available

208-230 V/60 Hz/3 phase

1,2

400 V/50 Hz/3 phase

1

400-460 V/50-60 Hz/3 phase Global Voltage

1,2

Standard Compliance

1

CE compliant

(for all ThermoFlex recirculating chillers)

105974_C_000

2

CSA compliant

Patented full flow filter ensures
clean fluid to protect your
application and maximize
recirculation system life.

Easily removable condenser
grill and air filter allow for
quick and simple cleaning to
optimize chiller performance
and maximize component life.

Patented integrated funnel design
allows for spill proof filling.

Specifications obtained at sea level using water as the recirculating fluid, at a +20°C process setpoint, +25°C ambient condition, at nominal operating voltage.
Other fluids, process temperatures, ambient temperatures, altitude or operating voltages will affect performance. Cooling capacity based on units with
P2 pumps with no backpressure. Other pumps will affect cooling capacity performance. Specifications subject to change.
**Pressure values for centrifugal and turbine pumps are differential pressures between the inlet and the outlet of the unit.