Discharging capacity, examples, Torkel 820 – Atec Megger-TORKEL-820 User Manual
Page 4
TORKEL 820
Battery Load Unit
Specifications TXL830 / 850
Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field
The instrument is intended for use in
high-voltage substations and industrial
environments.
Temperature
Operating
0°C to +40°C (32°F to +104°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity
5% – 95% RH, non-condensing
CE-marking
LVD
2006/95/EC
EMC
2004/108/EC
General
Mains voltage
100 – 240 V AC, 50 / 60 Hz
Power consumption
75 W (max)
Protection
Thermal cut-outs, automatic overload
protection
Dimensions
Instrument
210 x 353 x 600 mm
(8.3” x 13.9” x 23.6”)
Transport case
265 x 460 x 750 mm
(10.4” x 18.1” x 29.5”)
Weight
13 kg (28.7 lbs)
21.4 kg (47.2 lbs) with transport case
Cable sets for
TXL830 / 850
2 x 3 m (9.8 ft), 70 mm
2
, 270 A, with
cable lug. Max. 100 V. 5 kg (11 lbs)
Load section
TXL830
TXL850
Max. voltage (DC) 28 V
56 V
Max. current
300 A
300 A
Max. power
8.3 kW
16.4 kW
Internal resistance, 3-position selector
Position 1
TXL830
TXL850
Current
0.275 Ω
0.55 Ω
100 A
at 27.6 V (12 x 2.3 V) at 55.2 V (24 x 2.3 V)
78.5 A
at 21.6 V (12 x 1.8 V) at 43.2 V (24 x 1.8 V)
50.1 A
–
–
39.2 A
–
–
Position 2
TXL830
TXL850
Current
0.138 Ω
0.275 Ω
200 A
at 27.6 V
at 55.2 V (24 x 2.3 V)
156 A
at 21.6 V
43.2 V (24 x 1.8 V)–
Position 3
TXL830
TXL850
Current
0.092 Ω
0.184 Ω
300 A
at 27.6 V
at 55.2 V (24 x 2.3 V)
235 A
at 21.6 V
43.2 A (24 x 1.8 V)
100 A
–
–
78.4 A
–
–
Discharging capacity, examples
12 V battery (6 cells)
2)
Final voltage
Constant current
Constant power
1.80 V / cell (10.8 V)
0 – 121 A
0 – 1.31 kW
1.75 V / cell (10.5 V)
0 – 117 A
0 – 1.23 kW
1.67 V / cell (10.0 V)
0 – 110 A
0 – 1.10 kW
24 V battery (12 cells)
2)
1.80 V / cell (21.6 V)
0 – 270 A
0 – 5.8 kW
1.75 V / cell (21.0 V)
0 – 266 A
0 – 5.59 kW
1.60 V / cell (19.2 V)
0 – 241 A
0 – 4.63 kW
48 V battery (24 cells)
2)
1.80 V / cell (43.2 V)
0 – 270 A
0 – 11.6 kW
1.75 V / cell (42.0 V)
0 – 270 A
0 – 11.3 kW
1.60 V / cell (38.4 V)
0 – 259 A
0 – 9,9 kW
2) 2.15 V per cell when test starts