TORKEL 820

Battery Load Unit

Specifications TORKEL 820

Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.

Environment

Application field

The instrument is intended for use in
high-voltage substations and industrial
environments.

Temperature

Operating

0°C to +40°C (32°F to +104°F)

Storage & transport -40°C to +70°C (-40°F to +158°F)

Humidity

5% – 95% RH, non-condensing

CE-marking

LVD

2006/95/EC

EMC

2004/108/EC

General

Mains voltage

100 – 240 V AC, 50 / 60 Hz

Power consumption

150 W (max)

Protection

Thermal cut-outs, automatic overload
protection

Dimensions

Instrument

210 x 353 x 700 mm
(8.3” x 13.9” x 27.6”)

Transport case

265 x 460 x 750 mm
(10.4” x 18.1” x 29.5”)

Weight

22.3 kg (49.2 lbs)
40.4 kg (89.1 lbs) with accessories and
transport case

Display

LCD

Available languages

English, French, German, Spanish, Swe-
dish

Measurement section

Current measurement

Display range

0.0 – 2999 A

Basic inaccuracy

±(0.5% of reading +0.2 A)

Resolution

0.1 A

Internal current measurement
Range

0 – 270 A

Input for clamp-on ammeter
Range

0 – 1 V

mV/A-ratio

Software settable, 0.3 to 19.9 mV/A

Input impedance

>1 MΩ

Voltage measurement

Display range 0.0 – 60 V
Basic inaccuracy

±(0.5% of reading +0.1 V)

Resolution

0.1 V

Time measurement

Basic inaccuracy

±0.1% of reading ±1 digit

Load section

Battery voltage

10 – 60 V DC

Max. current

270 A

Max. power

15 kW

Load patterns

Constant current, constant power, con-
stant resistance, current or power profile

Current setting

0-270.0 A (2999.9 A)

1)

Power setting

0-15.00 kW (299.99 kW)

1)

Resistance setting

0.1-2999.8 Ω

Battery voltage range 2 ranges, selected automatically at start

of test

Stabilization (For
internal current meas-
urement)

±(0.5% of reading + 0.5 A)

Battery
voltage

Highest permissible
current

Resistor ele-
ment (Nominal
values)

Range 1 10 – 27.6 V 270 A

0.069 Ω

Range 2 10 – 55.2 V 270 A

0.138 Ω

1) Maximum value for a system with more than one load unit

Inputs, maximal values

EXTERNAL
CURRENT
MEASUREMENT
EXTERNAL
CURRENT

1 V DC, 300 V DC to ground. Current
shunt should be connected to the nega-
tive side of the battery

START / STOP

Closing / opening contact
Closing and then opening the contact will
start / stop Torkel. It is not possible to keep
the contacts in closed position.

Delay until start

200 – 300 ms

Stop delay

100 – 200 ms

Battery

60 V DC, 500 V DC to ground

VOLTAGE SENSE

60 V DC, 500 V DC to ground

SERIAL

< 15 V

ALARM

250 V DC 0.28 A
28 V DC 8 A
250 V AC 8 A

Outputs, maximal values

START / STOP

5 V, 6 mA

TXL

Relay contact

SERIAL

< 15 V

ALARM

Relay contact