beautypg.com

Features and benefits, Application examples with torkel/ txl systems – Atec Megger-TORKEL-820 User Manual

Page 2

background image

TORKEL 820

Battery Load Unit

13

12

11

10

9

3

1

4

2

5

6 7

8

TORKEL and the extra load TXL

Features and benefits

1.

Display

2.

External measurement input used to measure current in an ex-
ternal path by means of a clamp-on ammeter or a current
shunt.

3.

Keys for operation and settings.

4.

Alarm output equipped with a relay contact for triggering an
external alarm device.

5.

Start/Stop input used for starting and stopping discharging
from an external device. Galvanically isolated.

6.

Indicating lamps. Operating, Stop/Limit

7.

TXL output used for control of TXL Extra Loads. Galvanically iso-
lated.

8.

Serial port used for connection to a PC or other controlling
equipment.

9.

Voltage controlled circuit breaker that connects / disconnects
the loading circuits in TORKEL from the battery.

10.

Positive current connection for battery being tested.

11.

Input for sensing voltage at the battery terminals.

12.

Negative current connection for battery being tested.

13.

Mains connector, equipped with ON/OFF switch.

TORKEL / TXL - systems examples

Max. constant current
(A)

Number of TORKEL-
units

Number of
TXL-units

TORKEL 820 + TXL830, 12 V battery (6 cells)

1)

234

1

1

571

1

4

918

2

6

TORKEL 820 + TXL830, 24 V battery (12 cells)

1)

495

1

1

1170

1

4

1890

2

6

TORKEL 820 + TXL850, 48 V battery (24 cells)

1)

499

1

1

1189

1

4

1918

2

6

1) Discharge from 2.15 V to 1.8 V per cell

Application examples with TORKEL/

TXL systems

TORKEL and TXL can be combined into systems to match up for
different battery capacities. These resistive extra loads do not per-
form any regulating functions. They are designed for use together
with TORKEL Battery Load Units. Their purpose is to provide higher
load currents for use in constant current or constant power tests.
Together, TORKEL and the TXL Extra Loads form a system that can
discharge batteries with currents of up to several kA. TXL Extra
Loads are connected directly to the battery, and TORKEL measures
the total current using a clamp-on ammeter.
TXL Extra Loads are shut down automatically when TORKEL is
stopped.