Atec Megger-torkel-840-860 User Manual
Page 4
Programma
TORKEL 840/860 Battery Load Units
TORKEL/TXL Systems – Examples
TORKEL 820 + TXL830, 12 V battery (6 cells)
1
Max. constant current
Number of
Number of
(A)
TORKEL-units
TXL-units
234
1
1
571
1
4
918
2
6
TORKEL 820 + TXL830, 24 V battery (12 cells)
1
495
1
1
1170
1
4
1890
2
6
TORKEL 820 + TXL850, 48 V battery (24 cells)
1
499
1
1
1189
1
4
1918
2
6
TORKEL 840/860 + TXL830, 24 V battery (12 cells)
1
263
1
1
670
2
2
1005
3
3
TORKEL 840/860 + TXL850, 48 V battery (24 cells)
1
264
1
1
909
2
3
TORKEL 840/860 + TXL870, 110 V battery (54 cells)
1
188
1
1
532
2
4
845
2
8
TORKEL 840/860 + TXL870, 120 V battery (60 cells)
2
194
1
1
557
2
4
895
2
8
TORKEL 840/860 + TXL870, 220 V battery (108 cells)
1
94
1
1
266
2
4
423
2
8
1) Discharge from 2.15 V to 1.8 V per cell
2) Discharge from 2.15 to 1.75 V per cell
BATTERY TESTING ACCESSORIES
TORKEL Win
PC software
•Shows the complete voltage curve
• Last recorded time, voltage, current and discharged
capacity
• Scroll-window for all recorded values
• Remote control of TORKEL
• Report functions
TXL units
• Extra loads
• These resistive extra loads do not perform any
regulating functions.
• They are designed for use together with TORKEL Battery
Load Units.
• Their purpose is to provide higher load currents for use
in constant current or constant power tests. Together,
TORKEL and the TXL Extra Loads form a system that
can discharge batteries with currents of up to several kA.
TXL Extra Loads are connected directly to the battery,
and TORKEL measures the total current using a clamp-
on ammeter.
• TXL Extra Loads are shut down automatically when
TORKEL is stopped.
Cable Set GA-00550
TORKEL Win showing total voltage curve
TXL870