beautypg.com

Atec Megger-torkel-840-860 User Manual

Page 4

background image

Programma

TORKEL 840/860 Battery Load Units

TORKEL/TXL Systems – Examples

TORKEL 820 + TXL830, 12 V battery (6 cells)

1

Max. constant current

Number of

Number of

(A)

TORKEL-units

TXL-units

234

1

1

571

1

4

918

2

6

TORKEL 820 + TXL830, 24 V battery (12 cells)

1

495

1

1

1170

1

4

1890

2

6

TORKEL 820 + TXL850, 48 V battery (24 cells)

1

499

1

1

1189

1

4

1918

2

6

TORKEL 840/860 + TXL830, 24 V battery (12 cells)

1

263

1

1

670

2

2

1005

3

3

TORKEL 840/860 + TXL850, 48 V battery (24 cells)

1

264

1

1

909

2

3

TORKEL 840/860 + TXL870, 110 V battery (54 cells)

1

188

1

1

532

2

4

845

2

8

TORKEL 840/860 + TXL870, 120 V battery (60 cells)

2

194

1

1

557

2

4

895

2

8

TORKEL 840/860 + TXL870, 220 V battery (108 cells)

1

94

1

1

266

2

4

423

2

8

1) Discharge from 2.15 V to 1.8 V per cell

2) Discharge from 2.15 to 1.75 V per cell

BATTERY TESTING ACCESSORIES

TORKEL Win

PC software

•Shows the complete voltage curve

• Last recorded time, voltage, current and discharged

capacity

• Scroll-window for all recorded values

• Remote control of TORKEL

• Report functions

TXL units

• Extra loads

• These resistive extra loads do not perform any

regulating functions.

• They are designed for use together with TORKEL Battery

Load Units.

• Their purpose is to provide higher load currents for use

in constant current or constant power tests. Together,

TORKEL and the TXL Extra Loads form a system that

can discharge batteries with currents of up to several kA.

TXL Extra Loads are connected directly to the battery,

and TORKEL measures the total current using a clamp-

on ammeter.

• TXL Extra Loads are shut down automatically when

TORKEL is stopped.

Cable Set GA-00550

TORKEL Win showing total voltage curve

TXL870