TORKEL 840/860 Battery Load Units

Inputs, maximum values

External current

1 V DC, 300 V DC to ground. Current

measurement

shunt should be connected to the negative

side of the battery

Start/Stop

Momentary closure starts a test. Momentary

closure stops a test.

Delay until start

200 – 300 ms

Stop delay

100 – 200 ms

Battery

480 V DC, 500 V DC to ground

Voltage sense

480 V DC, 500 V DC to ground

Serial

< 15 V

Alarm

250 V DC 0.28 A 28 V DC 8 A

250 V AC 8 A

Outputs, maximum values

Start/Stop

5 V, 6 mA

TXL

Relay contact

Serial

< 15 V

Alarm

Relay contact

Discharging capacity examples

12 V battery (6 cells)

3

Final voltage

Constant current

Constant power

1.80 V/cell (10.8 V)

0 – 50.0 A

0 – 0.54 kW

1.75 V/cell (10.5 V)

0 – 49.0 A

0 – 0.51 kW

1.67 V/cell (10.0 V)

0 – 46.0 A

0 – 0.46 kW

24 V battery (12 cells)

3

1.80 V/cell (21.6 V)

0 – 110 A

0 – 2.37 kW

1.75 V/cell (21.0 V)

0 – 110 A

0 – 2.31 kW

1.60 V/cell (19.2 V)

0 – 100 A

0 – 1.92 kW

48 V battery (24 cells)

3

1.80 V/cell (43.2 V)

0 – 110 A

0 – 4.75 kW

1.75 V/cell (42.0 V)

0 – 110 A

0 – 4.62 kW

1.60 V/cell (38.4 V)

0 – 110 A

0 – 4.22 kW

110 V battery (54 cells)

3

1.80 V/cell (97.2 V)

0 – 110 A

0 – 10.7 kW

1.75 V/cell (94.5 V)

0 – 110 A

0 – 10.4 kW

1.60 V/cell (86.4 V)

0 – 110 A

0 – 9.5 kW

120 V battery (60 cells)

3

1.80 V/cell (108 V)

0 – 110 A

0 – 11.9 kW

1.75 V/cell (105 V)

0 – 110 A

0 – 11.5 kW

1.60 V/cell (96 V)

0 – 110 A

0 – 10.5 kW

220 V battery (108 cells)

3

1.80 V/cell (194 V)

0 – 55 A

0 – 10.7 kW

1.75 V/cell (189 V)

0 – 55 A

0 – 10.4 kW

1.60 V/cell (173 V)

0 – 51.0 A

0 – 8.82 kW

240 V battery (120 cells)

3

1.80 V/cell (216 V)

0 – 55 A

0 – 11.9 kW

1.75 V/cell (210 V)

0 – 55 A

0 – 11.5 kW

1.60 V/cell (192 V)

0 – 55 A

0 – 10.5 kW

UPS battery (180 cells)

3

(TORKEL 860)

1.70 V/cell (306 V)

0 – 38 A

0 – 15 kW

1.60 V/cell (288 V)

0 – 38 A

0 – 15 kW

UPS battery (204 cells)

3

(TORKEL 860)

1.80 V/cell (367 V)

0 – 34 A

0 – 15 kW

1.60 V/cell (326 V)

0 – 34 A

0 – 15 kW

3) 2.15 V per cell when test starts

Environment

Application field

The instrument is intended for use in high-

voltage substations and industrial

environments.

Temperature
Operating

0° C to +40° C (32° F to +104° F)

Storage & transport

-40° C to +70° C (-40° F to +158° F)

Humidity

5% – 95% RH, non-condensing

CE-marking

Safety standards

IEC 61010-1:2001 Incl. national dev. for US

and CAEN 61010-1:2001

EMC standards

EN 61326: 1997+A1:1998+A2:2001

General

Power supply voltage 100 – 240 V AC, 50/60 Hz

Power consumption

75 W (max)

Protection

Thermal cut-outs, automatic overload

protection

Dimensions
Instrument

210 x 353 x 600 mm (8.3” x 13.9” x 23.6”)

Transport case

265 x 460 x 750 mm (10.4” x 18.1” x 29.5”)

Weight

13 kg (28.7 lbs)21.4 kg (47.2 lbs) with

transport case

Cable sets
for TXL830/850

2 x 3 m (9.8 ft), 70 mm2, 270 A, with cable

lug. Max. 100 V. 5 kg (11 lbs)

for TXL870

2 x 3 m (9.8 ft), 25 mm2, 110 A, with cable

clamp/lug. Max. 480 V. 3 kg (6.6 lbs)

Load section

TXL830

TXL850

TXL870

Max. voltage (DC)

28 V

56 V

140 V/ 280 V

Max. current

300 A

300 A

112 A at 140 V

56 A at 280 V

Max. power

8.3 kW

16.4 kW

15.8 kW

Internal resistance, 3-position selector

Position 1

TXL830

TXL850

TXL870

Current

0.275

0.55

4.95

100 A

at 27.6 V

at 55.2 V

(12 x 2.3 V)

(24 x 2.3 V)

78.5 A

at 21.6 V

at 43.2 V

(12 x 1.8 V)

(24 x 1.8 V)

50.1 A

at 248.4 V

(108 x 2.3 V)

39.2 A

at 194.4 V

(108 x 1.8 V)

Position 2

TXL830

TXL850

TXL870

Current

0.138

0.275

2.48

200 A

at 27.6 V

at 55.2 V

(24 x 2.3 V)

156 A

at 21.6 V

43.2 V–

(24 x 1.8 V)

Position 3

TXL830

TXL850

TXL870

Current

0.092

0.184

1.24

300 A

at 27.6 V

at 55.2 V

(24 x 2.3 V)

235 A

at 21.6 V

43.2 A

(24 x 1.8 V)

100 A

at 124.2 V

(54 x 2.3 V)

78.4 A

at 97.2 V

(54 x 1.8 V)