beautypg.com

Atec Megger-SMRT36 User Manual

Page 3

background image

3

SMRT36

Megger Relay Test System

1. Binary Outputs 1 and 2: Rated for 300 V at 8 Amps.

2. Binary Inputs 1 and 2: Rated 5 to 300 V AC/DC.

3. Transducer Input: (Optional) DC voltage and DC milliamp

input terminals.

4. Voltage Outputs: Up to 3 channels 300 V at 150 VA,

convertible to currents 15 A at 120 VA per phase.

5. Current Outputs: Up to 3 channels 60 Amps at 300 VA per

phase. Up 180 Amps at 900 VA single phase.

6. USB 2.0 Interface: Communication and control port.

7. Additional Binary Inputs: Provides 8 additional monitor

circuits.

8. Rugged Case: Fiberglass reinforced plastic.

9. PC/OUT: Ethernet Port is the primary PC connection port.

Ethernet Port used to chain multiple SMRT units together for
synchronous multi-unit operation.

10. Additional Binary Outputs: Adds 4 outputs. Binary Outputs 3

and 4 are rated for 300 V AC/DC, 8 amperes. Binary Outputs 5
and 6 are high speed and have an AC/DC voltage rating of 400
volts peak, 1 ampere.

11. IN/61850: This port may also be used for connecting to the IEC

61850 substation bus for testing IEC 61850 devices.

12. STVI: Ethernet Port is a PoE (Power over Ethernet) port and is

used to connect to the STVI for manual control.

13. Battery Simulator: Variable 5 to 250 Volts DC output at 100

Watts (4 amperes maximum).

14. Incoming Power/Line Cord Socket: 100 to 240 V,

50/60 Hz.

15. POWER ON/OFF Switch: Illuminates when power is on.

16. Protective Earth Ground Jack.

17. Bluetooth: Bluetooth

©

provides wireless control.

ApplICATIONS SElECTION GuIDE

Protective Relays
by IEEE Device #

SMRT36

Single

Channel

SMRT36

Two

Channels

SMRT36

Three

Channels

2

Time Delay

n

n

n

21

Distance Single

Phase

n

n

n

21

Distance Three

Phase Open Delta

n

n

21

Distance Three

Phase wye

n

24

Volts/Hz

n

n

n

25

Synchronizing

n

n

27/59 Under/Over Voltage

n

n

n

32

Directional Power

Single Phase

n

n

n

32

Directional Power

Three Phase

(Open Delta)

(n)

n

37/76 DC Under/Over

Voltage/Current

n

n

n

40

Loss of Field

n

n

n

46

Phase Balance

Current

n

n

n

46N

Negative Sequence

Overcurrent

n

n

n

47

Phase Sequence

Voltage

(Open Delta)

(n)

n

50

Instantaneous

Overcurrent

Up to

75 Amps

Up to

150 Amps

Up to

225 Amps

51

Time Delay

Overcurrent

Up to

35 Amps

Up to

70 Amps

Up to

105 Amps

55

Power Factor

n

n

n

60

Voltage/Current

Balance

(Open Delta)

Single

Phase

(n)

n

67

Directional

Overcurrent

n

n

n

67N

Ground Directional

Overcurrent

n

n

n

78

Out of Step

n

n

n

79

Reclosing

n

n

n

81

Frequency

n

n

n

85

Carrier or Pilot Wire

n

n

n

87

Differential

n

n

n

91

Voltage Directional

(Open Delta)

(n)

n

92

Voltage and Power

Directional

(Open Delta)

(n)

n

94

Tripping

n

n

n

4

2

1

17

16

15

14

13

12

11

10

9

8

7

6

5

SMRT36 RElAy TESTER

3