DELTA3000

10 kV Automated Insulation Power Factor Test Set

SPECIFICATIONS

Input

120/230 V ±10%, 1

φ, 50/60 Hz, 1440 VA

Output

0 to 12 kV, continuously adjustable, 200 mA continuous;

310 mA maximum for up to 5 minutes.

The power supply capacity can be expanded to 4 Amps

using the optional Resonating Inductor, catalog number 670600.

Accuracy

Voltage
(RMS) ±(1% of reading + 1 digit)

Current
(RMS) ±(1% of reading + 1 digit)

Capacitance
±(0.5% of reading + 2 pF) in UST mode

±(0.5% of reading + 6 pF) in GST mode

Power Factor
±(2% of reading + 0.05%)

Dissipation Factor
±(2% of reading + 0.05%)

Watt Loss
±(2% of reading + 1mW)

Measuring Ranges

Voltage
250 V to 12 kV, 10 V resolution. Minimum recommended voltage

is 500 V.

Current
0 to 5 Amps, 1µA maximum resolution. The measurement can be

corrected to either 2.5 kV or 10 kV equivalents.

Capacitance
1 pF to 1.1 µF, 0.01 pF maximum resolution on low ranges.

Power Factor
0 to 90%, 0.01% maximum resolution.

Dissipation Factor
0 to 200%, 0.01% maximum resolution.

Watt Loss
0 to 2 kW, actual power, 0 to 100 kW when corrected to 10 kV

equivalent. 0.1 mW maximum resolution. The measurement can

be corrected to either 2.5 kV or 10 kV equivalents.

Measurement

The following seven test modes are available, using the blue and

red measuring leads, and can be selected by the operator:

UST: Ground Red, Measure Blue

UST: Ground Blue, Measure Red

UST: No Ground, Measure to both Red and Blue

GST: No Guard

GST: Guard Blue, Ground Red

GST: Guard Red, Ground Blue

GST: Guard Red, and Blue, No Grounding

UST: Ungrounded Specimen Testing

GST: Grounded Specimen Testing

Printer Interface

USB

Computer Interface

Ethernet

User Interface

8.4 in., full-color VGA, test forms on-screen view, full QWERTY

keypad and navigational pushbuttons

Data Storage

Internal: up to 100,000 data sets

External: USB flash device, up to 100,000 data sets

Communication/Control Software

PowerDB and PowerDB ONBOARD

Test Frequency

Same as line frequency

Interference Suppression

Available Suppression Methods

1. Operator selectable automatic forward/reverse measurement

averaging.

2. Operator selectable automatic tracking interference cancellation.

Safety Qualifications

The test set meets the requirements of both the IEC-1010 and the

CE mark specifications. The test set also meets the shock and

vibration requirements of the ASTM D999.75 standard.

Environment

Temperature
Operating:
32 to 122° F ( 0 to 50° C),

Storage: -58 to +140° F (-50 to +60° C)

Relative Humidity
Operating:
0 to 90% non-condensing

Storage: 0 to 95% non-condensing

Dimensions

Control Unit
16 H x 22 W x 16 D in.

(406 H x 559 W x 406 D mm)

High Voltage Unit
16 H x 22 W x 16 D in.

(406 H x 559 W x 406 D mm)

Weight

Control Unit: 74 lb (33kg)

High Voltage unit: 63 lb (29 kg)

Cables: 35 lb (16 kg)