DELTA3000

10 kV Automated Insulation Power Factor Test Set

Two optional high-voltage reference capacitors are

available to allow the user to perform a quick field check

to ensure the DELTA3000 has maintained its calibration. In

addition, an optional 10 nF TTR capacitor is available to

allow the user to perform high-voltage Transformer Turns

Ratio measurements with the DELTA3000.

The built-in tracking automatic interference suppression

circuit ensures accurate and reliable test results under

severe electrostatic and electromagnetic interference

conditions. This feature allows the performance of test

measurements in energized switchyards of up to 765 kV.

The Priority Access program provides specific support to

assure full utilization of the Megger DELTA3000. The

purchase of the program entitles the user to 24/7 support

services at an economical cost, with the first year provided

at no charge. (Applies to US market only.)

FEATURES AND BENEFITS

Fully automatic operation (stand-alone or remote-

control) with user interface via on-screen customizable

test forms.

Integrated PowerDB ONBOARD allows for data analysis

and trending while in the field without the use of an

external computer.

Built-in USB port and included USB printer allows for

8.5”x 11” or A4 test forms printing without the use of a

laptop.

Built-in capability for storing test results, in an open

XML format, to either internal memory or to an external

USB storage device.

Large 8.4” full VGA bright color display.

Performs all standard ungrounded-specimen tests (UST)

and grounded-specimen tests (GST), with or without a

guard circuit.

Built-in self diagnostic and calibration check.

Optional module to perform LV three-phase transformer

turns ratio testing and excitation current up to 500 mA in

accordance with Megger TTR330 product specifications.

Utilizing the automatic suppression circuitry achieves

high accuracy measurement under severe electrostatic

and electromagnetic interference conditions.

Two-piece design reduces size and weight of the system

and provides easier transportation.

The operator has the option of measuring either the

power factor or dissipation factor (tan

∂).

Open-ground detector ensures proper grounding before

test.

Interlock switches provide operator safety.

High accuracy SF6 gas-filled capacitor as internal

reference.

Built-in interface to the optional Resonating Inductor

(Cat. No. 670600) to extend the capacitance measuring

range to 1.1

µF at 10 kV.

Optional HV TTR capacitor (10 nF) in addition to two

HV reference capacitors (100 pF and 1000 pF) with a 2%

dissipation factor.

Optional USB bar code scanner to record and

alphanumeric test identification in the field.

Optional Priority Access package with exclusive services

(US market only).

Optional Oil Test Cell for testing insulating fluids up

to 10 kV.

Optional Calibration Standard verifies proper operation

and accuracy of the test results.

The DELTA3000, available in either 120 or 240 V ac/50 or 60 Hz,
includes the Control Unit (top) and High Voltage Unit (bottom)

Close-up of DELTA3000 panel