Harmonics, Events, Ordering information – Atec Fluke-1735 User Manual
Page 5: Optional accessories
5 Fluke Corporation 1735 Three-Phase Power Logger
Harmonics
Measuring range
Up to 50
th
harmonic (< 50 % of nom)
Accuracy:
Vm, Im, THDV, THDI
IEC 61000-4-7:00 Class II
Vm
≥ 3 % Vnom
± 5 % Vm
Vm < 3 % Vnom
± 0.15 % Vnom
Im
≥ 10 % Inom
± 5 % Im
Im < 10 % Inom
± 0 5 % Inom
THDV
for THD < 3 % ± 0.15 % at Vnom
for THD
≥ 3 % ± 5 % at Vnom
THDI
for THD < 10 % ± 0.5 % at Inom
for THD
≥ 10 % ± 5 % at Inom
Vnom: Nominal voltage range.
Inom: Nominal current range.
Vm and Im are measured values of harmonic m.
Events
Detection of voltage dips, voltage swells and voltage inter-
ruptions with a 10 ms resolution and measuring error of the
half period sine wave of rms.
Intrinsic error
± (1 % of m.v. + 10 digit)
Operating error
± ( % of m.v. + 10 digit)
Resolution
0.1 V
Fluke Corporation
PO Box 9090, Everett, WA USA 9806
Fluke Europe B.V.
PO Box 1186, 560 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (45) 446-5116
In Europe/M-East/Africa +31 (0) 40 675 00 or
Fax +31 (0) 40 675
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (45) 446-5500 or
Fax +1 (45) 446-5116
Web access: http://www.fluke.com
©006 Fluke Corporation. All rights reserved.
Printed in U.S.A. 5/006 63493 D-EN-N Rev A
Fluke. Keeping your world
up and running.
™
Ordering information
Fluke-1735
Power Logger
Includes:
•
Soft carrying case
•
4 flexible current probes (15 A/150 A/3000 A)
•
Power Log software
•
Voltage leads and clips
•
Color localization set
•
PC interface cable
•
International ac adapter (115/30 V, 50/60 Hz)
•
Printed English manual
•
Multi-language manual CD
Optional accessories
•
MBX Clamp 1 A/10 A – 3 precision dual range current
clamps (1 A/10 A) for secondary CT applications
•
MBX Clamp 5 A/50 A +N - 4 precision dual range
current clamps (5 A/50 A) for general applications
•
C435 – Water-tight hard case with rollers