MRCT

Megger Relay and Current Transformer Test Set

DeSCrIpTIonS oF HArDWAre opTIonS
AnD ACCeSSorIeS

relAY TeSTInG opTIon

DeSCrIpTIon

The MRCT can be configured to include the functionality to test
electromechanical, solid-state and microprocessor based over-
current relays, including voltage controlled, voltage restraint and
directional over-current; test under/over voltage, single-phase
impedance, single-phase power, directional, synchronizing, auto-
synchronizing, negative sequence under/over voltage, current
balance, frequency, volts/hertz, reclosing, thermal and various other
relays

ApplICATIonS

The current channel is rated for 30 amps @ 200 VA continuous, up
to 60 amps @ 300 VA for short durations. It has a unique flat power
curve from 4 to 30 amps that insures maximum compliance voltage
to load at all times. With a high compliance voltage of 50 volts the
SMRT1 has the capability to test high impedance over-current relays.
The voltage channel can provide a variable output of 0- 30/150/
300 Volts at 150 VA of output power, and has a unique flat power
curve from 30 to 150 volts insuring maximum output power to the
load at all times. With the voltage channel converted to current,
it can perform minimum operating point, slope and timing on
current differential relays, including harmonic restraint transformer
differential relays (which can be tested one phase at a time).

relAY opTIon SpeCIFICATIonS

outputs

All outputs are independent from sudden

changes in line voltage and frequency. This

provides stable outputs not affected by sudden

changes in the power source. All outputs are

regulated so changes in load impedance do not

affect the output.

output Current

Output power ratings are specified in

AC rms values and peak power ratings.

Output Current Power

Max V / Duty Cycle

1 ampere 15 VA 15.0 V rms continuous
4 amperes 200 VA (282 peak)

50.0 V rms continuous
15 amperes 200 VA (282 peak)

13.4 V rms continuous
30 amperes 200 VA (282 peak)

6.67 V rms continuous
75 amperes 300 VA (424 peak)

5.00 V rms 90 cycles
DC 200 Watts

AC Voltage output

Outputs are rated with the following Ranges:
Output volts power max I
30 volts 150 VA 5 amps
150 volts 150 VA (see Power V)
300 volts 150 VA 0.5 amps
DC 150 watts
Duty Cycle: Continuous

Metering

Measured output quantities such as AC amperes,

AC Volts, DC volts or DC amperes, and time may

be simultaneously displayed on the large, color

TFT LCD, optional STVI touch screen. The AC

and DC outputs display the approximate voltage/

current output prior to initiation of the outputs.

AC Voltage Amplitude

Accuracy

±0.05% reading + 0.02% range typical, ±0.15%

reading + 0.05% range maximum

Resolution

.01

Measurements

AC RMS

Ranges

30, 150, 300V

AC Current Amplitude

Accuracy

±0.05% reading + 0.02% range typical,

±0.15% reading + 0.05% range maximum

Resolution

.001/.01

Measurements

AC RMS

Ranges

30, 60A

DC Voltage Amplitude

Accuracy

0.1% range typical, 0.25% range maximum

Resolution

.01

Measurements

RMS

Ranges

30, 150, 300V

DC Current Amplitude

Accuracy

±0.05 % reading + 0.02 % range typical,

±0.15 % reading + 0.05 % range maximum

Resolution

.001/.01

Measurements

RMS

Ranges

30A