Mrct – Atec Megger-MRCT User Manual

Page 3

background image

MRCT

Megger Relay and Current Transformer Test Set

SpeCIFICATIonS

Input

100 to 132 V or 200 to 264 V, 1ø, 50 or 60 Hz,

15 A max.

output

Voltage

Continuously variable in three ranges:

0 to 30 V at 5.0 A max

(15 minute on, 5 minute off)

0 to 300 V at 1.0 A max

(15 minute on, 5 minute off)

300 to 2000 V at 1.0 A max

(5 minute on, 5 minute off)

Current

Output Current

Power Max V/Duty Cycle

30 Amperes

200 VA (282 peak) 6.67 V rms

(15 minutes on, 5 minutes off)

60 Amperes

600 VA 90 cycles

Instrumentation

Voltmeters
output

Resolution

0.0000 to 1.9999/19.999/199.99/1999.9

Ranges

0 to 2/20/200/2000 V

Accuracy

±0.5% of reading typical

±1.0% of reading typical max

Input

Primary Voltage

Measurement

Ranges

0 to 0.35/2.0/20.0/200.0/600.0 V

Resolution

0.0001 to 1.9999/19.999/199.9/600 V

Accuracy

±0.02% of reading and ±.02% range typical

±0.05% of reading and ±05% range maximum

Secondary Voltage Measurement

Ranges

0 to 2/20.0/200.0/2000.0 V

Resolution

0.0000 to 19.999/199.9/1999.9 V

Accuracy

0 to 999.9 V

±0.02% of reading and ±.02% range typical

±0.05% of reading and ±.05% range maximum

1000 to 2000 V

±0.08% of reading and ±.08% range typical

±0.2% of reading and ±0.2% range maximum

Ammeter

output

Ranges

0.0 to 1.0/10.0/60.0 A

Resolution

.001/.01

Input
excitation curve testing

Range

0.0000 to 0.1/1.0/8.0 A

Accuracy

±0.08% of reading ±.08% range typical

±0.2% of reading ±0.2% range maximum

phase Angle Measurement

3 digits

Range

0 to 360 degrees

Resolution

1 minute

Accuracy

±3 minuntes typical

±6 minutes maximum

ratio

Secondary Voltage Injection Method

Range

Accuracy

0.8 to 2000

±0.02% typical

±0.05% maximum

2000 to 5000

±0.03% typical

±0.1% maximum

5000 to 20000

±0.05% typical

±0.2% maximum

Winding resistance Test

Measuring Range

0 – 30 Ω

Accuracy

(at 20° C) ±1%, 0 – 30 Ω

Insulation Test

Test Voltage

1000 VDC, 500 VDC

Measuring Range

20 GΩ, 10 GΩ

Short Circuit Current

1.5 mA nominal

Test Current on Load

1 mA at min. pass values of insulation

(as specified in BS7671, HD 384 and IEC 364)

Accuracy

1000 volts ±3% ±2 digits ±0.2% per GΩ

500 volts ±3% ±2 digits ±0.4% per GΩ

Communication

Interfaces

Ethernet

environment

Operating

-10º C to 50º C

Storage

-30º C to 70º C

Enclosure

The unit is housed in a rugged enclosure suitable

for use in outdoor substations.

Standards

IEC 61010, CSA 22.2, CE

Dimensions

14” H X 7.5” W X 12” D

(36 H X 19.3 W X 30.5 D cm)

Weight

36.7 lb (16.7 kg)