4 Fluke Corporation Fluke 2680 Series Data Acquisition Systems

Key features of this powerful

development package include:

An extensive graphics library

Drag & drop programming

More than 140 device drivers

OPC client/server compliance

Support for DNA, OPC, DDE,
OBDC, XML, SOAP and Active X

Fluke 2680A-OPC: Create
custom applications using
OLE for Process Control

Optional Fluke 2680A-OPC soft-
ware gives you the freedom to
integrate your 2680 Series into
any OPC-compliant application.
Create custom applications using
2680A-OPC software and just
about any popular industrial soft-
ware package such as Wonder-
ware,

®

LabVIEW,

Test Point, or

Indusoft Web Studio, as well as
software from Canary Labs, Daisy
Labs, and others. Open, non-pro-
prietary OPC support enables you
to use the software you choose or
the software you create.

Fluke 2680A-DLL library:
For developing or modifying
applications

The 2680A DLL library is designed
for programmers who want to
develop or modify their own
applications for the 2680 Series,
using C++, Visual Basic, and other
languages.

Channel capacity
(2680A or 2686A)
20 to 120 channels per chassis
(6 analog input modules of 20
channels each)
One master alarm (open collec-
tor) per chassis
Communications:
10BaseT/100BaseT, TCP/IP via
RJ45 connector, Cat 5
Math functions
In addition to its analog and
digital input channels, each
system supports 60 computed
channels. Calculations include
time & rate, addition, subtrac-
tion, multiplication, division,
log, natural log, exponent,
square root, absolute value,
integer function and average.

2680A Series Specifications

Analog to digital converter
2680A-PAI:
18 bit, multi-slope
type
2680A-FAI: 16 bit, multi-slope
type
Common mode rejection
2680A-PAI:
AC: ≥120 dB (50/60 Hz, ±0.1%

max 1 kΩ source imbalance)

DC: ≥120 dB

2680A-FAI:
AC: ≥100 dB (50/60 Hz, ±0.1%

max 1 kΩ source imbalance)

DC: ≥100 dB
Normal mode rejection
50 dB @ 50/60 Hz, ±0.1%
Common mode voltage
maximum
2680A-PAI:
300 VDC or VAC
rms (channels 1.11); 150 VDC
or VAC rms (all other channels)
2680A-FAI: 50 VDC or 30 VAC
rms (all channels)

Measurement speed
(2680A-PAI)
Slow:
6 readings/second
nominal
Medium: 41 (50 Hz), 48 (60
Hz) readings/second nominal
Fast: 143 readings/second
nominal (5 readings/second for
VAC nominal, 140 readings/
second on 300Ω range,

37 readings/second on 3 MΩ

range)
Measurement speed
(2680A-FAI)
Slow:
45 (50 Hz), 54 (60 Hz)
readings/second nominal
Medium: 200 readings/second
nominal
Fast: 1000 readings/second
nominal (5 readings/second for
VAC nominal, 370readings/
second on 300Ω range,

44 readings/second on 3 MΩ

range)

2680A-DEVSW: Powerful HMI development software

Automatic language translation
at run-time

Internationalization using
Unicode

Web display and alarm paging

Support for imported graphics
formats

The ability to view multiple
clients from one web browser