beautypg.com

Personal and area monitors, Determining location and area coverage, T.o.c – Atec Narda-8800 Series User Manual

Page 5: A level of 10mw/cm, Previous next

background image

Personal and Area Monitors

///////////

435 MORELAND ROAD • HAUPPAUGE, NY 11788

USA TEL: 516 231-1700 • INT’L TEL: (1) 516 231-1390 • FAX (1) 516 231-1711

E-MAIL: [email protected] • www.nardaeast.l-3com.com

DETERMINING LOCATION AND AREA COVERAGE

To calculate where an area monitor should be mounted,

various considerations are necessary. They include:
1. Areas where personnel are likely to be present

2. Probable radiation emanation point (or points)

3. Size of the area to be monitored

4. Safety standard level being used

5. Frequency and wavelength
Figure 2 shows the typical relationship between distance

and the reduction of the field strength in terms of equiva-

lent power density in the far field. When calculating the

area a SMARTS can effectively monitor, first determine

where the unit is to be mounted and what the alarm thresh-

old level is. The minimum protection area is based on the

assumption that the energy at the source of a leak will not

be known. For example, if the SMARTS was located 10

feet (“X”) from the source of the energy and it reached its

threshold of 1mW/cm

2

, a level of 10mW/cm

2

(the stan-

dard) would be present at a distance of 3.16 feet (

x ) from

the source. Therefore, the minimum protected area would

be all points at a distance less than 6.84 (x-

x ) feet from

the SMARTS. If a failure results in a higher or lower

amount of energy at the source, then one could calculate

an even smaller “unprotected” area.
Most safety standards average exposure over a period of

six minutes. Therefore, an additional safety margin exists

since the SMARTS sounds its alarm in less than one sec-

ond and corrective action could be enacted quickly by re-

moving power or exiting the area).
Figures 3 and 4 represent a shelter-mounting application.

Figure 3 shows one SMARTS and its associated “safe”

zone. Figure 4 denotes the same shelter but with two

SMARTS installed. It may be advisable to use multiple

monitors depending on where the high power is gener-

ated or routed.

1

2

3

4

5

6

7

8

9

10

0.5

1.0

5.0

10

50

100

500

1000

mW/cm

2

1.0 mW/cm

2

0.5 mW/cm

2

0.2 mW/cm

2

Relative Distance (D)

Equivalent Power Density (S)

S at

D = 10

S at D

10

1.0

0.5

0.2

÷

1/2X

A=1/2Y-

÷

1/2Y

Y

X

*

Protected Area

or "Safe" Zone

Energy Source

Location Anywhere

on This Perimeter

SMARTS

(at 1/10 of Std.)

Point Where Energy

is 10 Times

Level at SMARTS

A

A

B

B

A=1/2Y- 1/2Y

B=1/2X- 1/2X

A=1/2Y- 1/2Y

B=1/2X- 1/2X

Y

X

*

*

Protected Area

or "Safe" Zone

Energy Source

Location Anywhere

on This Perimeter

SMARTS

(at 1/10th of Std.)

Point Where Energy

is 10 Times

Level at SMARTS

A

B

B

B

B

A

1/4Y

1/4Y

It is always best to make actual measurements before in-

stallation since calculations cannot account for the vari-

ous objects that can perturb the field. Measurements are

more critical when determining the mounting position for

the Models 8810 and 8815 as they may be located in the

near field, where field strengths are very difficult to calcu-

late. When monitoring a test stand where the energy

would leak from a defined area, the SMARTS should al-

ways be placed as close as possible to the operator or

technician. Ideally, the SMARTS and the person should

be located the same distance from the source.

Figure 2. Equivalent Power Denisity versus Distance from Source

Figure 3. Single SMARTS Installation

Figure 4. Dual SMARTS Installation

%

Previous

Next

T.O.C.