Instrument specifications – Atec AdaptivePowerSystems-1000 Series User Manual
Page 2

MODEL
1002
1003
1005
1010
1020
1030
1040
INPUT SPECIFICATIONS
Phase
1Ø/2W + ground
3Ø/3W + ground
Voltage
230V±15%
220, 240, 380, 415, 480V±10%
Frequency
47-63Hz
OUTPUT SPECIFICATIONS
Power rating
2kVA
3kVA
5kVA
10kVA
20kVA
30kVA
40kVA
Max Arms @
0-150 V
16.8 A
25.2 A
42 A
84 A
168 A
252 A
336 A
Max Arms @
0-300 V
8.4 A
12.6 A
21 A
42 A
84 A
126 A
168 A
Phase
1Ø/3W (L, N, G)
Voltage
Low Range
0-150V
HIgh Range
0-300V
Resolution
0.1V
Accuracy
±(1%+0.2V)
Frequency
Range
45-500Hz
Resolution
0.1Hz at 45-99.9Hz, 1Hz at 100-500Hz
Accuracy
±0.2%
Harmonic Distortion
≤1%(Resistance Load)
Crest Factor
≥3 to 1
Load Regulation
±0.5%
Protection
Over Current, Short Circuit, Over Temperature
Efficiency
≥85% (at full load)
Operating Temperature
32°-104°F, (0°-40°C), 80% Relative Humidity
Altitude
below 6500 feet
DISPLAYS AND CONTROLS
4 Digital LED meters
Frequency, Voltage, Current, Power or Power Factor (simultaneously)
PLC Remote Interface
M1, M2, M3, and Output On/Off
Memory
3 Programmable Memory Locations for Voltage, Frequency and Current
Calibration
Front Panel Calibration
Auto voltage adjust
Enable for improved voltage regulation within ±0.1V
MECHANICAL SPECIFICATIONS
2kVA
3kVA
5kVA
10kVA
20kVA
30kVA
40kVA
Dimensions (HxDxW) Inches
12x26x17
12x26x17
12x26x17
28x26x17
34x26x17
38x36x24
43x36x24
Weights (Kg/lbs)
60/132
65/143
80/175
200/440
315/695
465/1025
550/1210
©2003 ADAPTIVE POWER SYSTEMS, Irvine, CA, U.S.A. Subject to change without notice.
Cooling fans
Output curcuit breaker
Output connections
Input curcuit breaker
801 Hailey Street Ardmore, OK 73401
Direct: 949-752-8400 • Fax: 949-756-0838
Toll Free: 1-866-517-8400
www.adaptivepower.com
TM
APS1000-9/06
Instrument Specifications
Input connections
Casters