beautypg.com

Atec APS-FC200 Series User Manual

Page 2

background image

INPUT SPECIFICATIONS

Input Phase

1-phase / 2-wire + Ground

Input Voltage

115/230Vac ± 15%

OUTPUT SPECIFICATIONS

Power rating

500VA

1000VA

Max Arms @

0-150V

4.2A

8.4A

Max Arms @

0-300V

2.1A

4.2A

Phase

1-phase / 2-wire + Ground

Low Range

0-150V

High Range

0-300V

Resolution

0.1V

Accuracy

± (0.5% of setting+2 counts)

Range

45 - 500Hz

Resolution

0.1Hz at 45 - 99.9Hz, 1Hz at 100 - 500Hz

Accuracy

± 0.2%

Harmonic Distortion

≤ 0.5% (Resistive Load)

Crest Factor

≥ 4 to 1

Load Regulation

± 0.5% (Resistive Load)

Protection

Over-Current, Short-Circuit, Over-Temperature

Operating Temperature

32°F - 104°F (0°C - 40°C), 80% Relative Humidity

Altitude

Below 6,500 feet

DISPLAY AND CONTROLS

4 Digital LED meters

Frequency, Voltage, Current, Power or Power Factor (simultaneously)

Memory (Standard)

3 Memories, 3 Programmable Parameters per Memory for:

Voltage, Frequency, Current Limit

Calibration

Front Panel Calibration

Auto-Voltage Adjust

Provides improved voltage regulation to within ± 0.1V

MECHANICAL SPECIFICATIONS

Power Rating

500VA

1000VA

Dimensions (In.)

H/D/W

3.5 x 16 x 17

3.5 x 22 x 17

Wieght kg/lb

22/48

37/81

©2006 ADAPTIVE POWER SYSTEMS, Ardmore, OK, U.S.A. Subject to change without notice.

PLC Remote Interface

Output

Output

Input

Input

Input Power Selector

Input Power Selector

PLC Remote Interface

Fans

801 Hailey Street Ardmore, OK 73401

Direct: 949-752-8400 • Fax: 949-756-0838
Toll Free: 1-866-517-8400
www.adaptivepower.com

TM

FC200-11/06

MODEL

FC205

FC210

Voltage

(r.m.s.)

Frequency

FC205

FC210

Fans