Input characteristics, General characteristics, Functional characteristics – Atec CA-8332-8334 User Manual
Page 4
Configuring instrument via software: setup, recording and alarms modes.
Recorded and alarm data processing.
Graphic representation of data in Windows
TM
environment.
Data analysis in compliance with EN 50160 standard.
Screen printout and transient transfers in BMP format.
3D representation of harmonics.
Data to spreadsheet transfer (Excel).
Input characteristics
Voltages: phase-phase: 600 V TRMS
phase-neutral: 480 V TRMS
Currents: according to sensors
MN clamp:
2 A... 240 A
C clamp:
3 A... 1 200 A
AmpFLEX:
10 A... 3 000 A
PAC:
10 A... 1 000 A AC
10 A... 1 400 A DC
Adapter unit casing for external CT
S P E C I F I C AT I O N S
General characteristics
Power supply:
Mains: 110 V and 230 V
NiMH (9.6 V) rechargeable battery
Autonomy: 10 hours
Temperature for use: 0°... 50°C
Storage temperature: - 40°... 70°C
Standards: EN IEC 61010, 600 V cat. III, pollution 2
Double insulation for inputs and outputs
Dimensions (L x W x H):
180 x 55 x 240
Weight:
1.5 kg with battery
Frequency range: 40 - 70 Hz
Voltage accuracy:
± 0.5 %
Current:
± 0.5 %
Power:
± 1 %
Power factor: ± 0.01
Frequency:
± 0.01 Hz
THD (total harmonic distortion):
± 1 % L ± 2 pts
Energy: ± 1 % L
Sampling frequency: 12.8 kHz / channel at 50 Hz
Functional characteristics
Functions
C.A 8332
C.A 8334
Display
color LCD 320 x 240
color LCD 320 x 240
Memory
2 Mbytes
4 Mbytes
Battery
1800 mAh
3800 mAh
Harmonics
Yes
Yes + expert mode
Recording
Yes (limited)
Yes
Alarms
Yes Yes
Transients
No Yes
Mains
AC+DC AC+DC
Digital link
RS 232
RS 232
With the
around-the-neck
holder, making
measurements
is easy: operating
the instrument and
reading the displays
at the same time.