4 specifications, 0 introduction – Alpha Technologies ACS HP Series User Manual
Page 12

12
AIP900-0012-B0-001 Rev. A (01/2012)
Specifications
Electrical
Input:
Voltage:
Nominal:
208 to 250Vac
Operating:
187 to 312Vac
Extended:
187 to 90Vac (derated)
Phase:
1 or 3
Frequency:
45 to 70Hz
Current:
23A/module-nom. (130A Max@ 175ADC output)
Power:
4400W continuous/module
Power Factor:
>0.99 (50 to 100% load)
THD:
<5%
Efficiency:
>93%
Output:
Voltage:
90 to 160Vdc
Current:
35A/module-nom. (200A Max @ 110VDC)
Load Regulation:
Static <±0.5%
Line Regulation:
Static <±0.1%
Transient Response:
<±5% for 40 to 90% load step, 30ms recovery time
Ripple:
±30mVrms Battery Eliminator
Mechanical
Dimensions:
Standard
XL
mm:
1049 H x 622 W x 597 D
1806 H x 700 W x 622 D
in:
41.25 H x 24.5 W x 23.5 D
71.1 H x 27.55 W x 24.5 D
Weight:
100 kg (220 lbs) for 105A system
115 kg (253 lbs) for 105A system
Cabinet:
NEMA 1 (black finish)
NEMA 1 (black finish)
Environmental
Temperature
Standard:
-40˚ to 50°C (-40˚ to 122°F)
Extended:
-40˚ to 75°C (-40˚ to 167°F)
Storage:
-40˚ to 85°C (-40˚ to 185°F)
Humidity:
0 to 95% RH non-condensing
Elevation:
-500 to 2,800m (-1,640 to 9,186ft);
to 4,000m (13,124ft) derated to 40˚C (104˚F)
Audible Noise:
<55dBa @ 1m (3ft)
Ventilation:
Forced Air/Convection
MTBF:
>350,000 hours
Standard Features
Full graphic touch screen LCD with virtual alphanumeric and numeric keyboards
Modbus Protocol
Access GUI user interface via Internet browser through Ethernet port or RS-232 craft
port on CXC Controller
High interrupting current input and output breakers (10kA IC)
Reverse polarity protection
AC and DC surge suppression
Current limit protection
Soft start protection
Common Form C alarm relay contacts
High voltage shutdown
AC failure alarm
High/Low voltage alarm
Charger failure alarm
Positive/Negative ground fault alarm
DC output failure alarm
Standard Features (continued)
Control Functions
Automatic, scheduled, or manual float charging (adjustable)
Automatic, scheduled, or manual equalize charging (adjustable)
High/Low voltage alarm setting (adjustable)
Charge current limit (adjustable)
Automatic or manual battery testing
Battery capacity and runtime prediction
Temperature compensation
Daily Statistics: Minimum, maximum and average on input channels,
with date and time stamp
Battery current, rectifier current, and AC mains volt-
age for prior 90 days
Event Log:
On all events such as alarms, power on, any change
of state of the digital inputs, or other miscellaneous
events
Battery Log:
Battery health history on last 20 discharges, time of
discharge, and battery capacity
Options
Low voltage disconnect
DC Output Panel
Up to 10 x 2 Pole, 5-60A breakers (10kA IC) with alarm monitoring
DNP3 Level 2
Standards, Certifications
Safety:
EN 60950
UL 60950-1 (pending)
CSAC22.2 No. 60950-1-03
CE EN 60950, CB Scheme
Telcordia (Bellcore) GR-1089-CORE
EMC:
EN 55022 (CISPR 22)
EN 61000-3-2 EN 61000-3-3
EN 61000-4-2 EN 61000-4-3
EN 61000-4-4 EN 61000-4-5
EN 61000-4-6 EN 61000-4-11
ETS 300 019-1-1 ETS 300 019-1-2
ETS 300 753 IEC60950
ICES-003 Class B FCC Part 15 Class B
FCC Part 68